Voltage Drop Calculator

Pick a wire gauge, length and current to see the voltage drop in volts and as a percentage of the source voltage.

=
Quick answer: with the default inputs (120 V, 20 A, 100 ft, 1.59), the voltage drop is 6.35. At these inputs: drop as percentage = 5.29, voltage at load = 113.65. Change any input to update the result.
Voltage drop
—

What this calculator returns

Three numbers come back from one run: the drop in volts, the same drop as a percentage of the source voltage, and the voltage that actually reaches the load. At the defaults — 120 V, 20 A, 100 ft one way, 12 AWG copper — you get 6.35 V, 5.29% and 113.65 V at the far end.

The percentage is the number to judge against a target, because 6.35 V means very different things on a 120 V circuit and a 480 V feeder.

The formula and the factor of two

Vdrop = 2 · L · R · I

L is the one-way run length in feet, R is the conductor resistance per foot (the selector stores it per 1,000 ft), and I is the current in amps. The 2 is there because current makes the trip out to the load and back again, so the loop is twice the trench length.

R is the property that makes wire gauge matter. Resistance per 1,000 ft roughly halves for every three AWG steps, so 14 AWG at 2.525 Ω becomes 1.588 at 12, 0.999 at 10 and 0.628 at 8. Halving resistance halves the drop at the same current.

Why the loop, not the run

A 100 ft run of 12 AWG contains 200 ft of copper in the circuit. That is 0.318 Ω at the selector value of 1.588 Ω per 1,000 ft, and 20 A through it wastes 6.35 V and 127 W as heat along the cable. The wasted power rises with the square of current, so a 30 A load on the same wire loses 286 W.

Worked example at the defaults

Round trip: 2 × 100 ft = 200 ft. Resistance: 200 × 1.588 ÷ 1,000 = 0.3176 Ω. Drop: 20 A × 0.3176 Ω = 6.35 V. Percentage: 6.35 ÷ 120 = 5.29%. Voltage at the load: 120 − 6.35 = 113.65 V.

That 5.29% sits above the 3% branch-circuit target, so the defaults describe a run that should be upsized. Moving to 10 AWG cuts the drop to 4.00 V (3.33%), and 8 AWG brings it to 2.51 V (2.09%).

Drop by wire gauge at 20 A over 100 ft

WireΩ/1,000 ftDrop at 120 VPercentMax length for 3%
14 AWG2.52510.10 V8.42%36 ft
12 AWG1.5886.35 V5.29%57 ft
10 AWG0.9994.00 V3.33%90 ft
8 AWG0.6282.51 V2.09%143 ft
6 AWG0.3951.58 V1.32%228 ft
4 AWG0.2480.99 V0.83%363 ft

The last column is the practical one when you are planning a run: it is the longest one-way distance that keeps 20 A inside a 3% budget on a 120 V supply. Note that the length allowance grows faster than the gauge, which is why a single size jump can rescue a run that failed by a wide margin.

What moves the percentage

  • Current: drop is linear, so going from 20 A to 30 A turns 6.35 V into 9.53 V and 5.29% into 7.94%.
  • Distance: also linear, so a 200 ft run at the defaults doubles to 12.70 V and 10.58%.
  • Gauge: each three-step size change roughly halves resistance and the drop with it.
  • Source voltage: raising 120 V to 240 V halves the percentage for the same absolute drop, which is why long feeders run at higher voltage.
  • Conductor temperature: copper resistance climbs about 0.4% per °C, so a conductor at 75°C reads higher than a cold one.

The 3% and 5% rules

The usual design target is no more than 3% on a branch circuit and 5% across the whole system including the feeder. These figures are recommendations for efficiency and equipment performance rather than an absolute legal limit, but they matter in practice: a motor rated for 230 V that receives 216 V draws more current for the same output, runs hotter and may trip its overload.

Where people get it wrong

  • Entering the round-trip distance, which stacks with the built-in factor of two and doubles the answer.
  • Sizing by ampacity alone: 14 AWG carries 15 A safely but loses 8.42% over 100 ft, far past any efficiency target.
  • Mixing copper and aluminum tables, since aluminum of the same gauge has about 1.6 times the resistance.
  • Ignoring the load end: a 5.29% drop leaves 113.65 V, below the 114 V lower limit many appliances expect.

A related trap is assuming the breaker protects the wire from voltage drop. It does not. A 20 A breaker on 12 AWG will hold at 20 A indefinitely while the far end sags by 6 V. Ampacity prevents overheating; voltage drop is a separate performance check with its own arithmetic.

Sizing a run in practice

Work in this order: find the load current, pick the smallest gauge whose ampacity covers it, then check the drop at the real length. If the percentage exceeds your target, move up one or two sizes rather than shortening the building. For a 50 A load 200 ft away at 240 V, 6 AWG gives 2 × 200 × 0.000395 × 50 = 7.90 V, or 3.29%, while 4 AWG brings it to 4.97 V and 2.07%.

For the resistance side of the same circuit, the Ohm’s law calculator handles V = IR directly when you already know the loop resistance.

Frequently asked questions

Why is the length doubled in the formula?

Current travels out to the load and back to the source, so the conductor length is twice the one-way distance. A 100 ft run has 200 ft of copper and, at 12 AWG, 0.3176 Ω of resistance.

What voltage drop is acceptable?

Aim for under 3% on a branch circuit and under 5% for the whole system including feeders. At the defaults the drop is 5.29%, so the run needs a size or two of upsizing.

How much does 12 AWG drop at 20 A and 100 ft?

6.35 V, which is 5.29% of 120 V, leaving 113.65 V at the load. Moving to 10 AWG reduces it to 4.00 V and 3.33%.

How far can I run 12 AWG on a 20 A circuit?

About 57 ft one way if you want to stay inside 3% at 120 V. At 240 V the same wire reaches roughly 113 ft, because the percentage is measured against twice the voltage.

Does this work for aluminum wire?

The listed resistances are copper. Aluminum has about 1.6 times the resistance at the same gauge, so a 12 AWG aluminum conductor behaves more like 13 AWG copper and drops about 10.2 V in the default scenario.

How do I reduce voltage drop?

Use a thicker wire, shorten the run, lower the current or raise the source voltage. Doubling the gauge’s cross-section roughly halves the drop; going from 20 A to 15 A cuts it by 25%.

Does voltage drop waste power?

Yes. The default case dissipates 127 W in the cable, calculated as I²R with 20 A through 0.3176 Ω. At 30 A the loss rises to 286 W, which is why undersized long runs get warm.

What voltage actually reaches the load at the defaults?

113.65 V from a 120 V supply. Many appliances expect at least 114 V, so a 5.29% drop is already at the edge of acceptable performance even though the breaker never trips.

Can I use the one-way distance instead?

Enter the one-way length, not the round trip. The formula already includes the factor of two, so entering 200 ft for a 100 ft run reports 12.70 V and 10.58% instead of 6.35 V and 5.29%.

Is voltage drop a code violation?

Not by itself in most residential codes, which set ampacity and installation rules rather than efficiency targets. The 3% and 5% figures are widely adopted recommendations, and some local codes and equipment warranties do enforce them.

Method and sources

Calculation basis

Physical constants follow CODATA 2022 recommended values, and formulas follow standard physics definitions.

Last updated: November 18, 2026
Formula & data sources
  • Voltage drop = 2 × length × resistance per length × current; copper AWG resistances per NEC Chapter 9 Table 8 (75°C).

Cite this page

Reference formats
APA 7CalcSeed. (2026, November 18). Voltage Drop Calculator. https://calcseed.com/c/scientific/voltage-drop-calculator/
MLA 9"Voltage Drop Calculator." CalcSeed, 18 Nov. 2026, calcseed.com/c/scientific/voltage-drop-calculator/.
ChicagoCalcSeed. "Voltage Drop Calculator." Last modified November 18, 2026. https://calcseed.com/c/scientific/voltage-drop-calculator/

Related calculators

People also calculate