How Much Voltage Are You Losing in That Wire Run?
A 12 A load running 100 ft through 12 AWG copper drops VD = 2 x 10.75 x 12 x 100 / 6530 = 3.95 V, about 3.3 percent of a 120 V circuit, just over the 3 percent branch-circuit guideline.
A 12 A load running 100 ft through 12 AWG copper drops VD = 2 x 10.75 x 12 x 100 / 6530 = 3.95 V, about 3.3 percent of a 120 V circuit, just over the 3 percent branch-circuit guideline.
Why voltage drop matters
Every foot of conductor is a small resistor in series with the load, and the voltage it consumes is unavailable to the equipment at the far end. Lights dim, motors start hard and run hot, heaters underperform, and electronics reset on brownouts. Voltage drop is also pure loss: the power dissipated in the wire becomes heat in the wall, not work at the load. Sizing conductors for ampacity alone, without checking drop, is how long runs end up delivering 108 V to a 120 V appliance. The National Electrical Code addresses this through informational guidance rather than hard ampacity rules, which makes it the designer's job to check, and this guide shows the arithmetic behind that check.
The physics is simply Ohm's law applied to wire. Conductor resistance in ohms scales with length and inversely with cross-sectional area, and the area unit that wire tables use is the circular mil (cmil), the diameter of the wire in mils squared. One mil is 1/1000 of an inch. Everything in the standard voltage drop formula follows from those three ingredients: resistance per unit length, current, and distance.
The single-phase formula
VD is the voltage drop in volts, K the conductor resistivity constant in ohms per cmil-foot, I the load current in amperes, L the one-way run length in feet, and CM the conductor area in circular mils. The factor of 2 exists because a single-phase circuit has two current-carrying conductors, out and back, each the same length, each dropping voltage in the same direction as far as the loop is concerned. Three-phase circuits replace the 2 with 1.732. Using the one-way length with the built-in factor of 2 is the standard convention; do not double the length a second time.
K and circular mils
K expresses the resistance of a conductor one foot long with a cross-section of one circular mil. For copper, K ≈ 10.75 Ω·cmil/ft near 75°F; for aluminum the equivalent value is about 17.6, reflecting aluminum's higher resistivity for the same size. K is not truly constant: resistance rises with temperature, so a conductor running hot drops slightly more voltage than the cold value suggests. The circular mil areas of common sizes come straight from wire tables and are worth memorizing in round numbers.
| AWG size (copper) | Circular mils (CM) |
|---|---|
| 14 AWG | 4,110 |
| 12 AWG | 6,530 |
| 10 AWG | 10,380 |
| 8 AWG | 16,510 |
| 6 AWG | 26,240 |
Worked example, step by step
Take the case from the opening: a 12 A load, a 100 ft one-way run, 12 AWG copper. Step one, gather terms: K = 10.75, I = 12, L = 100, CM = 6,530. Step two, multiply: 2 x 10.75 = 21.5; 21.5 x 12 = 258; 258 x 100 = 25,800. Step three, divide: 25,800 / 6,530 ≈ 3.95 V. As a percentage of a 120 V circuit that is 3.95 / 120 ≈ 3.3 percent, slightly over the 3 percent branch-circuit guideline. Now compare conductors for the same load and run: 14 AWG gives 25,800 / 4,110 ≈ 6.28 V, or 5.2 percent, clearly too much; 10 AWG gives 25,800 / 10,380 ≈ 2.49 V, or 2.1 percent, comfortable. One wire size up solves a run that one size down ruins.
The simplified resistance method
When you already have the conductor resistance per 1000 ft from a table, the circular-mil step disappears. NEC Chapter 9, Table 8 lists DC resistance for uncoated copper at 75 °C, and those values plug directly into the formula. Using the hot conductor resistance makes the answer slightly more conservative than the K = 10.75 baseline, which is the right direction to err in.
| AWG size (uncoated copper) | R at 75 °C (Ω per 1000 ft) |
|---|---|
| 14 AWG | 3.07 |
| 12 AWG | 1.98 |
| 10 AWG | 1.24 |
| 8 AWG | 0.78 |
| 6 AWG | 0.49 |
The same 12 A, 100 ft, 12 AWG example through this route gives VD = 2 x 12 x 100 x 1.98 / 1000 ≈ 4.75 V, or 3.96 percent of 120 V. The difference from the 3.95 V result is entirely temperature: resistance at 75 °C exceeds the cooler K baseline by roughly 20 percent. Either method is defensible for design estimates; the conservative one is safer for long runs feeding motor loads.
What the code actually says
The National Electrical Code addresses voltage drop in an informational note to Section 210.19: branch circuit conductors sized so the drop does not exceed 3 percent, and total drop from service to the load not exceeding 5 percent. Informational notes are guidance, not enforceable rules, but the 3 / 5 split is widely written into specifications, energy codes, and manufacturer requirements, and inspectors and engineers treat it as the norm. For long runs, satisfying drop often means upsizing one or two AWG sizes above the ampacity minimum, and that cost is trivial next to rewiring a leg that starves a motor.
Variations worth knowing
Three-phase circuits replace the factor of 2 with √3 ≈ 1.732, giving VD = 1.732 x K x I x L / CM. For conductors roughly 1/0 AWG and larger, AC reactance begins to matter alongside DC resistance, and accurate drop calculations use effective impedance with the load's power factor, which is beyond the simple constant-K method. Low-voltage DC systems are the easiest case but the most sensitive in percentage terms: the same 4 V drop that is 3 percent of 120 V is 33 percent of a 12 V DC circuit, which is why 12 V landscape and automotive runs need careful sizing. As always, always verify final conductor sizing against the applicable code edition and local amendments, and engage a licensed electrician for installed work.
Common mistakes
- Doubling the length and keeping the factor of 2, which overstates drop by a factor of two. The formula's 2 already accounts for the return path.
- Using the round-trip length in a three-phase formula, mixing conventions between methods.
- Applying copper K to aluminum conductors. Aluminum needs the higher constant, roughly 17.6 in the same temperature band.
- Judging drop against 240 V when the load actually sees 120 V line-to-neutral, halving the percentage on paper only.
- Ignoring starting current. Motor inrush can be six times running current, and a marginal feeder that passes at rated load still starves the start.
Run the numbers before the wire goes in, not after the complaint call. The voltage drop calculator evaluates all the variants above, and the AWG to metric converter helps when drawings and wire stock come from different unit worlds. A two-minute calculation per run is the cheapest insurance in electrical work.
Calculators for this project
Frequently asked questions
Is the 3 percent rule legally mandatory?
The 3 percent branch and 5 percent total figures appear in an informational note to NEC 210.19, which is guidance rather than an enforceable section. However, specifications, energy codes, and equipment manufacturers frequently make them binding, and good practice treats them as the default.
Why is there a 2 in the single-phase formula?
A single-phase circuit has two conductors carrying the load current, out and back. Each drops voltage, and the load sees the sum. The factor of 2 covers the return conductor when L is the one-way run length.
Does voltage drop waste energy?
Yes. The power lost in the conductor is I²R, dissipated as heat in the wall. A long undersized run both starves the load and raises the utility bill, which is why dropping the drop pays twice.
How does 240 V compare to 120 V for the same run?
The drop in volts is identical, but as a percentage it halves on a 240 V circuit: a 3.95 V drop is 3.3 percent of 120 V but only 1.6 percent of 240 V. High-voltage or split-wiring arrangements therefore tolerate longer runs at the same wire size.
Method and sources
- NFPA 70, National Electrical Code (NEC), Chapter 9 Table 8 and Section 210.19 Informational Note
- Ugly's Electrical References (Jones & Bartlett Learning)