Ventilation Calculator
Enter the room dimensions and air changes per hour to find the required airflow in CFM.
What the number means
The calculator returns the room volume in cubic feet and the airflow in CFM, cubic feet per minute. A 20 ft by 15 ft room with an 8 ft ceiling holds 2,400 cu ft, and at 6 air changes per hour it needs 240 CFM. That is the airflow a fan or duct has to move continuously to swap the whole volume six times an hour.
The formula, term by term
Volume is length × width × height, all in feet. A room with a sloped ceiling or a vaulted section needs the average height, not the peak. For a 20 × 15 room that rises from 8 ft to 12 ft at the ridge, the average is 10 ft and the volume is 3,000 cu ft, not 2,400.
Air changes per hour is how many times the full volume is replaced in an hour. Six is a common figure for a bathroom or utility room. It is a rate, not an efficiency, so a leaky room and a tight room at the same ACH move the same air; the tight room just gets more of it through the fan.
Dividing by 60 converts hours to minutes. 2,400 cu ft × 6 = 14,400 cu ft per hour, and 14,400 ÷ 60 = 240 cu ft per minute. Skipping the divide gives 14,400, a size no residential duct carries.
Worked example at the defaults
Room 20 ft × 15 ft × 8 ft, 6 ACH. Volume: 20 × 15 = 300 sq ft of floor, × 8 = 2,400 cu ft. Airflow: 2,400 × 6 = 14,400, ÷ 60 = 240 CFM.
A 240 CFM fan is a large bathroom or small kitchen fan. Most 4 in ceiling fans move 50–110 CFM, and most 6 in fans move 150–300 CFM, so this room sits at the top of the 6 in class. The next standard size up is 300 CFM at 7.5 ACH.
Check what the number does not cover. 240 CFM through a 6 in duct is 240 ÷ 0.196 = 1,224 ft per minute, which is loud and lossy. The same air through an 8 in duct runs at 688 ft per minute. The CFM is the requirement; the duct has to be sized for it separately.
Same room, one variable changed
Hold the room at 2,400 cu ft and move ACH only. At 4 ACH the fan is 160 CFM, at 8 ACH it is 320, and at 12 ACH it is 480. Doubling the air change rate doubles the fan, the duct, the make-up air and the energy bill, so pick the rate from the room use rather than from a catalogue.
Airflow by air change rate
| Air changes | Cubic feet per hour | CFM for 2,400 cu ft |
|---|---|---|
| 2 ACH | 4,800 | 80 |
| 4 ACH | 9,600 | 160 |
| 6 ACH | 14,400 | 240 |
| 8 ACH | 19,200 | 320 |
| 10 ACH | 24,000 | 400 |
| 12 ACH | 28,800 | 480 |
| 15 ACH | 36,000 | 600 |
| 20 ACH | 48,000 | 800 |
Every row is the same 2,400 cu ft room. The middle column is what the room needs in an hour, and the right column is that figure divided by 60. For a different room, scale the CFM by volume: a 1,200 cu ft room at 6 ACH needs 120 CFM, exactly half.
Air change rates by room
| Room | Example volume | Typical ACH | CFM |
|---|---|---|---|
| Bedroom | 12 × 12 × 8 = 1,152 cu ft | 5 | 96 |
| Living room | 20 × 15 × 8 = 2,400 cu ft | 4 | 160 |
| Bathroom | 8 × 5 × 8 = 320 cu ft | 8 | 43 |
| Kitchen | 12 × 10 × 8 = 960 cu ft | 15 | 240 |
| Basement | 20 × 15 × 8 = 2,400 cu ft | 8 | 320 |
These rates are rules of thumb, not code. The kitchen number is high because it assumes the exhaust hood captures grease and moisture at the cooktop; a 240 CFM hood on a 30 in range is mid-range, and professional ranges ask for 600–1,200 CFM. The bathroom number looks small at 43 CFM because a 320 cu ft powder room is small, which is exactly why the prescriptive minimum matters more than the ACH result there.
When code minimums beat the ACH math
ASHRAE 62.2 sets bathroom exhaust at 50 CFM intermittent or 20 CFM continuous, and kitchen exhaust at 100 CFM intermittent or 25 CFM continuous. The 320 cu ft bathroom above calculates to 43 CFM at 8 ACH, which is under the 50 CFM floor, so the fan must be 50 CFM regardless of what the ACH table says.
Whole-house ventilation uses a different formula: 0.03 CFM per sq ft of conditioned floor area plus 7.5 CFM per bedroom plus one. A 2,000 sq ft three-bedroom house needs 0.03 × 2,000 + 7.5 × 4 = 90 CFM of continuous outdoor air.
Local exhaust or whole-house
Local exhaust removes moisture and odor at the source: a bathroom fan, a range hood. Whole-house ventilation dilutes indoor pollutants everywhere and runs continuously at low speed. A 240 CFM bathroom fan does not substitute for a 90 CFM ERV, and an ERV does not clear a shower in ten minutes.
Undersizing and oversizing
- Undersized bathroom fan: a 43 CFM fan in a 320 cu ft bath leaves the mirror fogged for 15 minutes and feeds mould in the grout.
- Oversized bathroom fan: 200 CFM in the same room pulls 200 CFM of conditioned air out and needs 200 CFM of make-up air through the door gap.
- Oversized kitchen hood: above 400 CFM, most codes require a make-up air system, which adds $800–$2,500.
- Undersized duct: a 240 CFM fan on a 4 in duct is over 2,700 ft per minute, which triples the static pressure and cuts real airflow by half.
The energy side is easy to underestimate. Moving 240 CFM of outdoor air into a house at a 30°F indoor-outdoor difference costs about 240 × 1.08 × 30 = 7,776 BTU/h, or roughly 0.65 tons of cooling in summer and the equivalent heat in winter. An ERV recovers 60–75% of that, which is why cold-climate installations pair continuous ventilation with heat recovery.
Duct, fan and controls
Size the duct for 700–900 ft per minute on a short run. A 240 CFM fan wants an 8 in duct at 688 fpm; a 6 in duct at 1,224 fpm is too fast and will howl. Every 90 degree elbow adds the equivalent of 5–10 ft of straight pipe, and a 4 in wall cap adds about 30 ft.
- Rate the fan at 0.25 in wg, not free air: a 240 CFM fan often delivers 180 CFM under load.
- A 240 CFM fan wants an 8 in duct; 6 in pushes velocity to 1,224 ft per minute.
- Over 25 ft of run or three elbows, move up one fan size.
Controls matter as much as the fan. A 20 minute delay timer clears a bathroom after a shower; a humidistat runs the fan only when the room is above 60% relative humidity. For continuous whole-house ventilation, a 90 CFM ERV running at 50% duty moves the same daily air as a 45 CFM unit running flat out, at lower noise.
Frequently asked questions
How do I calculate CFM for a room?
Multiply length × width × height to get cubic feet, multiply by air changes per hour, then divide by 60. A 20 × 15 × 8 room at 6 ACH is 2,400 × 6 ÷ 60 = 240 CFM.
How many CFM for a 200 sq ft room?
At an 8 ft ceiling and 6 ACH, 200 × 8 = 1,600 cu ft, and 1,600 × 6 ÷ 60 = 160 CFM. At 4 ACH the same room needs 107 CFM.
What is a good air change rate for a bathroom?
Eight air changes per hour is the working rule, but never below 50 CFM intermittent per ASHRAE 62.2. A 320 cu ft powder room calculates to 43 CFM, so the 50 CFM floor wins.
How many CFM for a kitchen exhaust hood?
One hundred CFM intermittent is the code minimum, and 15 ACH is the comfort rule. A 960 cu ft kitchen at 15 ACH needs 240 CFM, and pro-style ranges ask for 600–1,200 CFM.
Why do I divide by 60?
Air changes are per hour and CFM is per minute. 14,400 cu ft per hour divided by 60 minutes gives 240 cu ft per minute.
How many air changes per hour does a bedroom need?
Four to six. A 12 × 12 × 8 bedroom is 1,152 cu ft, so 5 ACH is 96 CFM if the room is ventilated mechanically rather than by an open door.
Is 240 CFM too much for a bathroom fan?
Yes for a normal bathroom. A 240 CFM fan suits a large room of about 2,400 cu ft; a 40–60 sq ft bathroom wants 50–80 CFM, or the fan pulls conditioned air out faster than the door can supply make-up air.
What size duct for 240 CFM?
Eight inches. That is 688 ft per minute, inside the 700–900 fpm target. A 6 in duct moves the same air at 1,224 fpm and will be noisy.
Does a range hood count as whole-house ventilation?
No. A hood is local exhaust and only runs while cooking. Whole-house ventilation is continuous and sized by the 0.03 CFM per sq ft plus 7.5 per bedroom rule.
How much does ventilation heat loss cost?
About 7,800 BTU/h for 240 CFM at a 30°F difference. An ERV at 70% recovery cuts that to roughly 2,300 BTU/h.
Method and sources
- CFM = volume × ACH ÷ 60; recommended air changes by room type.