Duct Size Calculator

Enter the airflow in CFM and air velocity to find the required duct area and diameter.

=
Quick answer: with the default inputs (800 CFM, 900 ft/min), the duct area is 128. At these inputs: round duct diameter = 12.77. Change any input to update the result.
Duct area
—

What this calculator finds

Duct sizing is a two-step conversion: airflow divided by air velocity gives the cross-section the air needs, and the cross-section converts to a round duct diameter. At the defaults — 800 CFM at 900 ft/min — the required area is 128 sq in, which corresponds to a round duct of 12.77 in, so a 13 in round duct or its rectangular equivalent is the right pick.

How the formula works

A=QvA=\frac{Q}{v}

The units do the hidden work here. Dividing CFM (cubic feet per minute) by feet per minute leaves square feet, which the calculator converts to square inches by multiplying by 144. For the default case: 800 ÷ 900 = 0.889 sq ft, and 0.889 × 144 = 128 sq in.

For a round duct, area converts to diameter through A = π × (d/2)², so d = 2√(A/π). With 128 sq in: 2√(128/3.1416) = 2√40.74 = 12.77 in. Ducts come in standard diameters (4, 5, 6, 7, 8, 9, 10, 12, 14, 16, 18, 20 in), so you round to the nearest standard size and accept the small velocity change that comes with it.

Design velocity targets

  • Supply trunks typically run 700 to 900 feet per minute.
  • Branch runs can be a bit lower to keep noise down.
  • Return ducts are usually sized one standard size larger to cut friction.
  • Undersized ducts raise static pressure and strain the fan.

Residential systems are quiet at or below about 900 fpm in main trunks and 600–700 fpm in branches near living spaces. Above roughly 1,000 fpm, ducts start to whistle and registers hiss; below 400 fpm, ducts get large and expensive without meaningful benefit.

Worked example at the defaults

A 2.5-ton air handler moves about 1,000 CFM, but a single 800 CFM trunk branch is a common design case. At the default velocity: 800 ÷ 900 × 144 = 128 sq in of cross-section, and 2√(128/π) = 12.77 in of round diameter. The nearest standard round duct is 13 in (or 14 in where 13 in is unavailable), which slows the actual velocity to about 865 fpm — comfortably inside the quiet band.

If you size that same 800 CFM at a branch velocity of 600 fpm instead, the required area rises to 192 sq in and the diameter to about 15.7 in — a 16 in duct. That is the trade in a nutshell: lower velocity means quieter operation, larger ducts, and more material and ceiling space.

CFM to round duct size at 900 ft/min

Airflow (CFM)Required areaDiameterStandard round duct
10016 sq in4.5 in5 in
20032 sq in6.4 in7 in
40064 sq in9.0 in9 in
60096 sq in11.1 in12 in
800128 sq in12.8 in13 in
1,200192 sq in15.6 in16 in
1,600256 sq in18.1 in18 in

The table shows the pattern that matters in the field: duct area scales directly with CFM, but diameter scales with the square root, so doubling airflow only increases diameter by about 41%. Going from an 800 CFM trunk to a 1,600 CFM trunk takes you from 13 in to 18 in, not 26 in.

Rectangular equivalents

Where a 13 in round duct does not fit, match the area in rectangular form: a 14 × 9 in duct gives 126 sq in, and a 10 × 13 in duct gives 130 sq in — both close to the 128 sq in target. Keep the aspect ratio under about 4:1 when you flatten ducts; a 28 × 4.5 in duct may have the same area, but its extra friction surface chokes airflow in practice. The deeper the rectangular duct, the closer it performs to round.

Undersizing versus oversizing

An undersized duct raises velocity, and friction losses grow with roughly the square of velocity — a duct squeezed from 13 in to 10 in on the same 800 CFM runs at 1,450 fpm and can double the static pressure that segment adds to the system. The blower compensates by running harder, which cuts delivered CFM, raises noise and shortens motor life. Oversizing is the safer error: a 14 in duct on this load runs near 840 fpm, costs a few dollars more in metal, and quietly improves both noise and efficiency. When in doubt, take the next standard size up.

Where sizing fits in the whole system

A duct is one segment of a friction budget. Manual D design allocates an available static pressure — typically 0.5 in w.c. after subtracting the coil, filter and register losses — across the entire trunk-and-branch network, and each segment must fit that budget at its design friction rate of about 0.08–0.1 in per 100 ft. Sizing every run by velocity alone can still leave a long trunk that steals friction from the far branches. Use this calculator per run, then check total external static against the air handler rating; system-level sizing is where a professional Manual D pays for itself.

Common mistakes when sizing ducts

  • Using the blower’s rated CFM for every branch — divide system airflow across runs by room load, not equally.
  • Sizing returns the same as supplies; return ducts should be one size larger because they carry the same CFM at lower design velocity.
  • Ignoring flex duct stretch — flex installed stretched straight performs near its nominal size, but sagging or compressed flex can cut effective diameter by 20–30%.
  • Forgetting that every elbow adds friction equivalent to several feet of straight duct.
  • Matching area with flat, wide rectangles that exceed a 4:1 aspect ratio.

Relating duct size to equipment size

Duct sizing starts with airflow, and airflow starts with equipment capacity: one ton of cooling needs about 400 CFM in standard-humidity climates. A 3-ton system therefore moves roughly 1,200 CFM, and per the table above its trunk needs about 192 sq in — a 16 in round duct. If you have not fixed the equipment size yet, the HVAC size calculator sets tons first, and this tool converts the resulting CFM into duct dimensions room by room.

Frequently asked questions

How do I size a duct for CFM?

Divide the airflow by the target velocity to get the cross-section, then pick a round or rectangular duct of that area. For 800 CFM at 900 ft/min that is 128 sq in, or a 13 in round duct.

What velocity should ducts use?

Around 700 to 900 feet per minute is common for main supply trunks, 600–700 ft/min for branches near living spaces, and lower still for returns.

What size duct do I need for 800 CFM?

At 900 ft/min, 128 sq in of cross-section, which is a 12.8 in round duct — use a 13 in or 14 in standard size, or a 14 × 9 in rectangular equivalent.

Does a bigger duct help?

A larger duct lowers velocity and noise but costs more and needs more space. Stepping 800 CFM from 13 in to 14 in drops velocity to about 840 fpm, which is usually a quiet improvement worth the small cost.

What happens if a duct is too small?

Velocity and friction rise sharply — an 800 CFM run squeezed into a 10 in duct operates near 1,450 fpm and can double that segment’s static pressure, cutting delivered airflow and raising noise.

How many CFM per ton of cooling?

About 400 CFM per ton in standard-humidity climates, so a 3-ton system moves roughly 1,200 CFM and needs a 16 in round trunk at 900 ft/min.

Can I use rectangular duct instead of round?

Yes, as long as the cross-section area matches — 128 sq in is a 14 × 9 in duct. Keep the aspect ratio under about 4:1 because flat ducts add friction.

Is flex duct as good as metal duct?

Stretched straight and supported, flex performs close to its nominal size. Compressed or sagging flex can lose 20–30% of effective diameter, so metal is preferred for long trunks.

Why do return ducts run larger than supply ducts?

Returns carry the same CFM but are designed at lower velocity to reduce fan suction noise and friction, which typically means one standard size larger than the matching supply run.

What diameter is a 128 sq in duct?

Exactly 2√(128/π) = 12.77 in. Since ducts come in standard sizes, you round to 13 in or 14 in and the actual velocity shifts only slightly.

Method and sources

Calculation basis

Cost ranges reflect 2026 U.S. national averages for materials and labor; regional pricing varies, so use results as a planning baseline and confirm with local quotes.

Last updated: November 17, 2026
Formula & data sources
  • Duct area = CFM ÷ velocity; round duct area = π × (d/2)².

Cite this page

Reference formats
APA 7CalcSeed. (2026, November 17). Duct Size Calculator. https://calcseed.com/c/home/duct-size-calculator/
MLA 9"Duct Size Calculator." CalcSeed, 17 Nov. 2026, calcseed.com/c/home/duct-size-calculator/.
ChicagoCalcSeed. "Duct Size Calculator." Last modified November 17, 2026. https://calcseed.com/c/home/duct-size-calculator/

Related calculators

More Home & DIY calculators