Circuit Breaker Size Calculator
Enter the continuous load current to find the breaker rating the circuit requires.
What this calculator does
This tool applies the NEC 125% continuous-load rule to find the breaker a circuit requires. Enter the continuous load current in amps — the current a device draws for three hours or more — and the calculator multiplies by 1.25 and rounds up to the next standard breaker size. A 16 amp continuous load requires a 20 amp breaker at the defaults.
The 125% rule
A breaker protects the wire, not the appliance, and it is designed to run indefinitely at 100% only in short bursts. The NEC treats any load running three hours or more as continuous and requires sizing the breaker and conductor at 125% of that load — equivalently, the breaker may carry no more than 80% of its rating continuously. This is why a 20 amp circuit should host no more than 16 amps of continuous load, and why the calculator returns 20 for a 16 amp input: 16 is exactly 80% of 20.
Worked example at the defaults
A continuous load of 16 A: 16 × 1.25 = 20 A minimum, which lands exactly on a standard 20 A breaker — the pairing behind every code-compliant kitchen countertop small-appliance circuit, sized for 12 AWG copper. Bump the load to 17 A and the requirement becomes 21.25 A, forcing the next standard size, 25 A, which in turn needs 10 AWG wire. One amp of load can therefore change the wire gauge, which is why this arithmetic belongs before the wire is bought, not after.
Load, breaker, and wire pairs
| Continuous load | Required amps (×1.25) | Breaker | Copper wire |
|---|---|---|---|
| 12 A | 15 A | 15 A | 14 AWG |
| 16 A | 20 A | 20 A | 12 AWG |
| 24 A | 30 A | 30 A | 10 AWG |
| 32 A | 40 A | 40 A | 8 AWG |
| 40 A | 50 A | 50 A | 6 AWG |
| 48 A | 60 A | 60 A | 6 AWG |
Wire sizes are typical residential copper ratings without correction factors; aluminum conductors and high ambient temperatures derate differently. The 40 A row is the familiar hardwired water-heater circuit, and the 48 A row is why a 48 amp Level 2 EV charger on a 60 A breaker is such a common garage project — it matches the continuous-load rule exactly. In 2026, a standard 15–20 A breaker costs $10–$30, a 50–60 A breaker $30–$80, and running new circuit wiring adds $2–$6 per foot.
Standard breaker sizes
The calculator rounds up to one of the standard ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 amps. Sizes below 15 A exist for special loads but are uncommon in residential panels, and anything above 200 A belongs to service equipment rather than a branch circuit.
What the 80% limit really forbids
- A space heater pulling 15 A continuously on a 15 A circuit — legal only because a heater is thermostat-cycled, but marginal for a long session
- A 20 A circuit supplying 19 A for hours — the breaker holds, but the wire runs near its thermal limit with no margin
- An EV charger drawing 40 A on a 40 A breaker — not allowed; 40 A continuous needs a 50 A breaker, which is why chargers ship with a 32 A default on 40 A circuits
- Two 12 A loads sharing one 20 A kitchen circuit — 24 A total breaks the 16 A continuous ceiling even though neither device overloads alone
Common mistakes
- Sizing the breaker to the wire you already ran instead of the load — the load comes first, then the breaker, then the wire
- Treating intermittent loads as continuous — loads under three hours may size at 100%, but when in doubt the 125% rule is the safe default
- Ignoring simultaneous trips — a breaker protects against overcurrent, not against two devices sharing an undersized circuit
- Upsizing the breaker to stop nuisance trips — trips signal overloaded wiring or a failing device; a bigger breaker hides the problem and can start a fire
- Mixing wire gauges mid-circuit — the smallest conductor anywhere on the run sets the maximum breaker for the whole circuit
When to involve an electrician
Swapping a like-for-like breaker is within reach of a careful DIYer; adding or resizing a circuit is not, because it touches the panel, the load calculation for the whole dwelling, and often permits. Many jurisdictions require a licensed electrician for anything inside the panel, and inspection is mandatory when the work is permitted. Costs to keep in mind: adding a dedicated circuit runs $150–$500, a 240-volt EV circuit with a 50–60 A breaker runs $500–$1,500 depending on distance, and a panel upgrade to 200 A runs $1,500–$4,000. Size the circuit correctly once with this calculator, then confirm conductor choice with the wire size calculator before buying materials.
Frequently asked questions
What is the 125% rule?
The NEC requires continuous loads — anything running three hours or more — to be sized at 125% of rated current, so the breaker and wire never run at their limits. A 16 A continuous load needs a 20 A breaker.
Why can a breaker carry only 80% of its rating?
Breakers are calibrated to trip if run at 100% of rating for extended periods. Sizing at 125% of the load is the same statement as limiting continuous current to 80% of the breaker rating.
What breaker does a 16 amp load need?
16 × 1.25 = 20, so a 20 A breaker on 12 AWG copper. That pairing is exactly the 80% continuous ceiling of a standard kitchen small-appliance circuit.
What size breaker for a 48 amp EV charger?
48 A continuous × 1.25 = 60 A, so the charger goes on a 60 A breaker with 6 AWG copper conductors. Setting the charger to 40 A instead allows a 50 A breaker.
Can I put a bigger breaker on the same wire?
No. The breaker must never exceed the ampacity of the conductor it protects — 14 AWG tops out at 15 A, 12 AWG at 20 A and 10 AWG at 30 A in standard residential copper.
What if the load is intermittent?
Loads that never run three hours or more may be sized at 100% of current, so a 15 A intermittent load can sit on a 15 A breaker. The 125% rule remains the safe default whenever the duty cycle is uncertain.
What are the standard breaker sizes?
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175 and 200 amps. The calculator rounds your requirement up to the next size on that list.
How much does it cost to add a circuit in 2026?
A dedicated 120 V circuit runs $150–$500 installed, a 240 V 50–60 A EV circuit $500–$1,500 depending on run length, and a full 200 A panel upgrade $1,500–$4,000.
Why does my breaker keep tripping even though nothing feels hot?
Nuisance trips usually mean the continuous load exceeds the 80% ceiling, a device draws inrush that mimics an overload, or the breaker itself is aging. Fix the load, not the breaker — never upsize without re-checking the wire gauge.
Does the 125% rule apply to the wire too?
Yes. The conductor must carry 125% of the continuous load as well, so the breaker size and wire ampacity are chosen together — a 60 A continuous-load circuit needs both a breaker and wire rated above 75 A.
Method and sources
- NEC 125% continuous-load rule and standard circuit breaker ratings.