Wire Size Calculator
Enter your load current and wire run length to find the minimum safe wire gauge and the expected voltage drop.
What this calculator does
A conductor is sized by ampacity — the current it can carry without overheating — and then checked against voltage drop, which is how much voltage the long run itself consumes. This calculator applies both tests: it multiplies your load current by 1.25 for the continuous-load rule, matches the result to a standard copper gauge, and reports the voltage drop that gauge produces over your run length. At the defaults — a 20 A load over a 50 ft one-way run at 120 V — the minimum ampacity is 25 A, the recommended wire is 10 AWG, and the drop is about 2 V (1.66%).
How the ampacity rule works
The 125% factor mirrors the NEC continuous-load rule: anything running three hours or more may use only 80% of a conductor’s rating, and sizing the wire at 125% of the load is the same statement from the other side. For the default 20 A load, 20 × 1.25 = 25 A of required ampacity. In the gauge table, 12 AWG is rated 20 A and 10 AWG is rated 30 A, so the wire that satisfies the rule is 10 AWG — even though 12 AWG would physically carry 20 A for short bursts.
How the voltage drop check works
Every gauge has a fixed resistance in ohms per 1,000 ft. Voltage drop is V = 2 × length × current × resistance ÷ 1,000 — the factor of 2 accounts for current traveling out on one conductor and back on the other. With 10 AWG’s resistance of 0.9989 Ω per 1,000 ft, the default run drops 2 × 50 × 20 × 0.9989 ÷ 1,000 = 1.998 V, which is 1.66% of 120 V — well inside the 3% branch-circuit target. If the drop had exceeded your max-drop setting, the fix is stepping up one or two gauges until it fits.
Worked example at the defaults
Double the run to 100 ft and the interplay shows clearly. The ampacity answer does not change — 20 A × 1.25 = 25 A still calls for 10 AWG. But the drop becomes 2 × 100 × 20 × 0.9989 ÷ 1,000 = 3.996 V, or 3.33% of 120 V, just over the 3% limit. Stepping up to 8 AWG (0.6282 Ω per 1,000 ft) drops the same 100 ft run to 2.51 V, or 2.09% — passing. This is the classic pattern: ampacity sets the floor, and long runs force you above it.
Copper gauge table: ampacity and resistance
| Wire | Ampacity rating | Resistance (Ω per 1,000 ft) | Typical use |
|---|---|---|---|
| 14 AWG | 15 A | 2.525 | Lighting and receptacle circuits |
| 12 AWG | 20 A | 1.588 | Kitchen and bathroom receptacles |
| 10 AWG | 30 A | 0.9989 | Water heaters, window AC, dryers (with 30 A breaker) |
| 8 AWG | 40 A | 0.6282 | Ranges, long feeder runs |
| 6 AWG | 55 A | 0.3951 | Subpanels, EV chargers |
| 4 AWG | 70 A | 0.2485 | Large feeders |
The three sizes to memorize for household work: 14 AWG pairs with a 15 A breaker, 12 AWG with a 20 A breaker, and 10 AWG with a 30 A breaker. Never pair a gauge with a larger breaker than its rating — the breaker exists to protect the wire, not the appliance.
What affects the number
- Load current — the only input that changes the ampacity floor; every 5 A of load adds 6.25 A of required ampacity.
- Run length — drop is linear in length: 50 ft of 10 AWG at 20 A drops 1.66%, 150 ft drops 5%.
- Voltage — a 240 V circuit tolerates the same absolute volt drop over twice the distance, since 4 V is 3.3% of 120 V but only 1.7% of 240 V.
- Ambient temperature — conductors in spaces above 86°F must be derated per NEC 310 tables.
- Conductor material — aluminum conducts about 61% as well as copper, so it needs two gauge sizes larger for the same job.
Voltage drop thresholds and why they matter
The NEC recommends (but does not strictly require) keeping branch-circuit drop under 3% and combined feeder-plus-branch drop under 5%. Motors are the loads that punish you for ignoring it: a motor rated for 230 V that receives 219 V draws more current, runs hotter, and loses torque. Practical 2026 guidance: hold 3% on runs feeding motors and sensitive gear, and accept up to 5% on a rarely loaded lighting leg only when re-running heavier wire is impractical.
When length forces an upsize
- A 20 A circuit on 12 AWG stays within 3% up to about 56 ft one-way; past that, move to 10 AWG.
- A 30 A load on 10 AWG passes 3% only out to roughly 45 ft at 120 V — but over 180 ft at 240 V.
- A 50 A EV-charger circuit at 240 V on 6 AWG holds 3% past 100 ft; longer runs step to 4 AWG.
Copper versus aluminum
Copper is the default for branch circuits and what the resistance table here assumes. Aluminum costs meaningfully less per amp and is standard for utility service entrance and large feeders, but it requires two sizes larger (4 AWG aluminum ≈ 6 AWG copper in ampacity), anti-oxidant paste, and Al/Cu-rated terminations, because aluminum expands and contracts more with heat cycles and loose connections are the failure mode. Small-gauge solid aluminum branch wiring from the 1960s–70s is a known hazard and a red-flag inspection item. For anything 10 AWG and smaller, buy copper.
Common mistakes when picking wire
- Sizing wire to the breaker instead of the load — the load (times 1.25 if continuous) sets minimum ampacity; the breaker protects that wire.
- Using 14 AWG on a 20 A circuit because it fits the outlet; 14 AWG is rated 15 A and the pairing is prohibited.
- Ignoring voltage drop on runs past about 50 ft — the ampacity answer alone understates the gauge for long runs.
- Forgetting the out-and-back factor of 2 in drop math.
- Bundling many conductors in one conduit without applying conduit-fill and bundling derating.
Matching wire, breaker and load together
The three decisions form one chain: load current sets ampacity, ampacity sets gauge, and gauge sets the maximum breaker. For the default case, a 20 A continuous load requires 25 A of ampacity, 10 AWG satisfies it, and the breaker should be 30 A or smaller — but no larger than the load actually needs, so a 25 A or 30 A breaker is correct while a 40 A is not. If your circuit feeds a single dedicated appliance, the nameplate amps are your input; if it feeds general receptacles, use the connected-load approach in the electrical load calculator first, then bring that current figure here. Conduit packing is a separate check covered by the conduit fill calculator.
Frequently asked questions
What gauge wire for a 20 amp circuit?
12 AWG copper is the standard choice for a 20 amp circuit and is required whenever the run is short. If the load is continuous, the 125% rule pushes the minimum ampacity to 25 A and 10 AWG becomes the compliant pick.
Why multiply current by 1.25?
Continuous loads must be sized at 125% of their rated current so the wire does not overheat during sustained use — the same rule that limits a load to 80% of a breaker rating.
Does a longer run need thicker wire?
Yes. A 20 A load on 10 AWG drops 1.66% over 50 ft but 3.33% over 100 ft; past the 3% threshold you step up to 8 AWG.
What is an acceptable voltage drop?
Keep branch-circuit voltage drop under about 3%; 5% combined with the feeder is the common upper limit. Motors and pumps should stay at the tighter 3% figure.
What is the voltage drop on 50 feet of 12 AWG at 20 amps?
2 × 50 × 20 × 1.588 ÷ 1,000 = 3.18 V, which is 2.65% of 120 V — inside 3%, but the ampacity rule still calls for 10 AWG on a continuous 20 A load.
Can I use 14 AWG for a 20 amp breaker?
No — 14 AWG is rated 15 A, so a 20 A circuit requires 12 AWG or larger.
Copper or aluminum wire?
Copper carries more current per gauge and is standard for branch circuits; aluminum needs two sizes larger plus Al/Cu-rated terminations and is mainly used for service entrances and large feeders.
How far can I run 10 AWG wire on a 30 amp circuit?
At 120 V, 10 AWG holds the 3% drop limit to roughly 45 ft. At 240 V the same wire reaches about 180 ft, because the same absolute volt drop is a smaller percentage.
What wire do I need for a 240 V 50 A circuit?
The ampacity floor is 50 × 1.25 = 62.5 A for a continuous load, which calls for 6 AWG copper; for a non-continuous 50 A load, 6 AWG still fits and holds the 3% drop limit past 100 ft at 240 V.
Why does the calculator recommend 10 AWG for a 20 amp load?
The 125% continuous-load rule makes the minimum ampacity 25 A. 12 AWG is rated 20 A and 10 AWG is rated 30 A, so 10 AWG is the smallest gauge that satisfies the rule.
Method and sources
- NEC 125% continuous-load rule; copper conductor ampacity and resistance tables.