Current Density Converter
Convert electric current density between units in real time. Enter a value, choose the from and to units, and read the result instantly.
What current density measures
Current density is how much current passes through each unit of cross-sectional area, so it decides whether a conductor heats up, a plating bath deposits evenly, or a battery electrode degrades. The SI unit is A/m², but almost nobody uses it: wire tables quote A/mm² and electrochemistry quotes mA/cm². At the defaults, 1 A/mm² converts to 100 A/cm².
Because every unit differs only in the area, the conversion is a ratio of areas: result = value × factor(from) ÷ factor(to), with the factors counting how many A/m² each unit represents.
Why the factors step by 100 and 10,000
A square centimetre holds 100 square millimetres, so the same current spread over a cm² is 100 times less dense than over a mm²: 1 A/mm² = 100 A/cm². A square metre holds 10,000 cm² or 1,000,000 mm², giving the 10,000 and 1,000,000 factors. All three are exact integers, so this converter carries no rounding error at all — every digit you see is real.
The milliamp unit needs one extra step. One milliamp is 0.001 A and one cm² is 0.0001 m², so 1 mA/cm² = 0.001 ÷ 0.0001 = 10 A/m². That factor of 10 is why millamp-per-centimetre figures look small next to amp-per-square-metre ones: 20 mA/cm² is 200 A/m².
Worked example at the default settings
Convert 1 A/mm² to A/cm²: 1 × 1,000,000 ÷ 10,000 = 100 A/cm². The same density is 1,000,000 A/m² or 100,000 mA/cm².
Now attach it to a real conductor. A 1 mm² wire at 1 A/mm² carries 1 A. A 2.5 mm² twin-and-earth cable rated 20 A runs at 20 ÷ 2.5 = 8 A/mm², or 0.08 A/cm². A 1 oz copper PCB trace 1 mm wide has a cross-section of 0.035 mm², so carrying 2 A puts it at 57 A/mm² — high, but tolerable because the trace is short and the board spreads the heat.
Typical current densities by application
| Application | A/mm² | A/cm² | mA/cm² |
|---|---|---|---|
| House wiring, continuous | 5–8 | 0.05–0.08 | 500–800 |
| Transformer winding | 2–4 | 0.02–0.04 | 200–400 |
| Copper busbar | 1–2 | 0.01–0.02 | 100–200 |
| PCB trace, 1 oz, short | 30–60 | 0.3–0.6 | 3,000–6,000 |
| Electroplating bath | 0.0001–0.001 | 0.01–0.1 | 10–100 |
| Li-ion cell, fast charge | 0.0005–0.002 | 0.005–0.02 | 5–20 |
The table shows why unit choice follows the industry. Wiring sits between 5 and 8 A/mm², which reads as awkward decimals in A/cm², so millimetres win. Electroplating runs at 2–10 A/dm², and a square decimetre is 100 cm², so the same process is 0.02–0.1 A/cm² or 20–100 mA/cm² — the last form is what most plating datasheets print.
Where the conversion bites in practice
- Wire sizing: ampacity tables are per conductor size, not per unit area, so 20 A on 2.5 mm² is 8 A/mm² but 20 A on 6 mm² is only 3.3 A/mm².
- Plating thickness: at 20 mA/cm² copper deposits about 0.4 µm per minute, so doubling the density halves the bath time.
- Battery fast charge: 1C on a 5 Ah cell with about 1,000 cm² of electrode works out near 5 mA/cm², and a 4C charge pushes it to about 20 mA/cm², close to the graphite limit before lithium plating.
- Fuse and fault behaviour: a 100 A/mm² surge for milliseconds is survivable, while the same density for seconds melts copper.
Where the density actually concentrates
Average density across a component is rarely the number that fails. Current crowds into whatever metal is narrowest: a 1 mm trace that necks to 0.3 mm at a via has a third of the area, so 57 A/mm² in the wide section becomes 190 A/mm² at the neck. The same happens at connector pins, fuse links and the contact spots inside a relay, where real contact area can be a thousandth of the apparent area and local density reaches 10,000 A/mm².
Why A/mm² and A/cm² get confused
The numbers 1 and 100 are close enough in a hurry to look like a rounding difference rather than a hundredfold one. A design copied from a 3 A/mm² spec into a 3 A/cm² calculation under-sizes the conductor by 100 times and turns a cool cable into a heating element. The reverse mistake over-sizes by the same factor, which is expensive rather than dangerous but still wrong.
Temperature rise is the other hidden variable. Ampacity figures assume a stated ambient and a stated allowable rise, often 30 °C over 30 °C ambient for cable in free air. The same 8 A/mm² that is fine in a ventilated tray is not fine in a bundled conduit, where derating factors of 0.5 to 0.7 apply.
Derating turns a table value into a real one
Published densities assume a single circuit in free air at 30 °C ambient with a 30 °C rise. Four circuits bundled together apply a factor near 0.8, a conduit adds another 0.7, and a 40 °C plant room takes 0.87 off. Multiply them and a nameplate 8 A/mm² becomes 8 × 0.8 × 0.87 = 5.6 A/mm² before any conduit, or 3.9 inside one. The conversion arithmetic is exact; the engineering is not.
Precision and reporting
Every factor here is exact, so a conversion of 1 A/mm² to A/cm² returns exactly 100 with no floating-point residue. The uncertainty comes from the physical data, not the arithmetic: conductor area is nominal and can be 2–5% under for stranded cable, and current density in a PCB trace is not uniform because copper necks at vias and corners.
Mistakes to avoid
- Reading 1 A/mm² as 1 A/cm². It is 100 A/cm², so the first figure describes a far cooler conductor.
- Converting A/dm² straight to A/cm² without dividing by 100. A 4 A/dm² bath is 0.04 A/cm² or 40 mA/cm².
- Treating 1 oz copper as 1 mm thick. It is 35 µm, 28 times thinner, which is why PCB densities look extreme.
- Comparing densities measured at different temperature rises: 40 A/mm² at 10 °C rise is not the same duty as 40 A/mm² at 60 °C rise.
Frequently asked questions
How many A/cm² is 1 A/mm²?
Exactly 100, because a square centimetre contains 100 square millimetres. The same density is 1,000,000 A/m² or 100,000 mA/cm².
How do I convert mA/cm² to A/m²?
Multiply by 10. A 20 mA/cm² plating current is 200 A/m², and 5 mA/cm² is 50 A/m².
What is a safe current density for copper wire?
Roughly 3–6 A/mm² for continuous duty in free air, which is 0.03–0.06 A/cm². House wiring runs higher, 8 A/mm² for 20 A on 2.5 mm², because short runs and insulation ratings allow it.
What current density does electroplating use?
Typically 2–10 A/dm², which is 0.02–0.1 A/cm² or 20–100 mA/cm². A dm² is 100 cm², so dividing the A/dm² figure by 100 gives A/cm².
Why does the SI unit A/m² give such big numbers?
Because a square metre is a million square millimetres. A modest 5 A/mm² in a wire is 5,000,000 A/m², so the SI unit is reserved for physics and plasma work rather than wiring.
Is current density constant across a conductor?
No. At DC it is nearly uniform except at corners and constrictions; at high frequency the skin effect pushes current to the surface, so a 10 kHz current in a 10 mm conductor flows in a layer about 0.66 mm deep.
How does 1 oz copper translate to current density?
1 oz copper is 35 µm thick, so a 1 mm wide trace has 0.035 mm². Carrying 2 A gives 2 ÷ 0.035 = 57 A/mm², which is normal for short PCB traces.
What is the difference between ampacity and current density?
Ampacity is the total current a conductor can carry, in amps; current density divides that by area. A 2.5 mm² cable rated 20 A has an ampacity of 20 A and a density of 8 A/mm².
Does the converter round the result?
No. All four factors are exact powers of ten, so 1 A/mm² to A/cm² returns 100.0000 with no rounding error beyond display precision.
Method and sources
- Linear conversion through A/m²: result = value × factor(from) ÷ factor(to).
- Factors applied: 1 A/cm² = 10000 A/m²; 1 A/mm² = 1000000 A/m²; 1 mA/cm² = 10 A/m².
- Every factor is an exact decimal SI prefix of the base unit, so no rounded constant is involved.
- Every factor is an exact definition or an exact decimal SI prefix, so the only error is the floating-point rounding of the arithmetic itself.