Convert electric current density between units in real time. Enter a value, choose the from and to units, and read the result instantly.

=
Current Density Converter — convert between A/m², A/cm², A/mm² and more.
Result
—

What current density measures

Current density is how much current passes through each unit of cross-sectional area, so it decides whether a conductor heats up, a plating bath deposits evenly, or a battery electrode degrades. The SI unit is A/m², but almost nobody uses it: wire tables quote A/mm² and electrochemistry quotes mA/cm². At the defaults, 1 A/mm² converts to 100 A/cm².

Because every unit differs only in the area, the conversion is a ratio of areas: result = value × factor(from) ÷ factor(to), with the factors counting how many A/m² each unit represents.

result=value×factor(from)factor(to)result = value imes rac{factor(from)}{factor(to)}

Why the factors step by 100 and 10,000

A square centimetre holds 100 square millimetres, so the same current spread over a cm² is 100 times less dense than over a mm²: 1 A/mm² = 100 A/cm². A square metre holds 10,000 cm² or 1,000,000 mm², giving the 10,000 and 1,000,000 factors. All three are exact integers, so this converter carries no rounding error at all — every digit you see is real.

The milliamp unit needs one extra step. One milliamp is 0.001 A and one cm² is 0.0001 m², so 1 mA/cm² = 0.001 ÷ 0.0001 = 10 A/m². That factor of 10 is why millamp-per-centimetre figures look small next to amp-per-square-metre ones: 20 mA/cm² is 200 A/m².

Worked example at the default settings

Convert 1 A/mm² to A/cm²: 1 × 1,000,000 ÷ 10,000 = 100 A/cm². The same density is 1,000,000 A/m² or 100,000 mA/cm².

Now attach it to a real conductor. A 1 mm² wire at 1 A/mm² carries 1 A. A 2.5 mm² twin-and-earth cable rated 20 A runs at 20 ÷ 2.5 = 8 A/mm², or 0.08 A/cm². A 1 oz copper PCB trace 1 mm wide has a cross-section of 0.035 mm², so carrying 2 A puts it at 57 A/mm² — high, but tolerable because the trace is short and the board spreads the heat.

Typical current densities by application

ApplicationA/mm²A/cm²mA/cm²
House wiring, continuous5–80.05–0.08500–800
Transformer winding2–40.02–0.04200–400
Copper busbar1–20.01–0.02100–200
PCB trace, 1 oz, short30–600.3–0.63,000–6,000
Electroplating bath0.0001–0.0010.01–0.110–100
Li-ion cell, fast charge0.0005–0.0020.005–0.025–20

The table shows why unit choice follows the industry. Wiring sits between 5 and 8 A/mm², which reads as awkward decimals in A/cm², so millimetres win. Electroplating runs at 2–10 A/dm², and a square decimetre is 100 cm², so the same process is 0.02–0.1 A/cm² or 20–100 mA/cm² — the last form is what most plating datasheets print.

Where the conversion bites in practice

  • Wire sizing: ampacity tables are per conductor size, not per unit area, so 20 A on 2.5 mm² is 8 A/mm² but 20 A on 6 mm² is only 3.3 A/mm².
  • Plating thickness: at 20 mA/cm² copper deposits about 0.4 µm per minute, so doubling the density halves the bath time.
  • Battery fast charge: 1C on a 5 Ah cell with about 1,000 cm² of electrode works out near 5 mA/cm², and a 4C charge pushes it to about 20 mA/cm², close to the graphite limit before lithium plating.
  • Fuse and fault behaviour: a 100 A/mm² surge for milliseconds is survivable, while the same density for seconds melts copper.

Where the density actually concentrates

Average density across a component is rarely the number that fails. Current crowds into whatever metal is narrowest: a 1 mm trace that necks to 0.3 mm at a via has a third of the area, so 57 A/mm² in the wide section becomes 190 A/mm² at the neck. The same happens at connector pins, fuse links and the contact spots inside a relay, where real contact area can be a thousandth of the apparent area and local density reaches 10,000 A/mm².

Why A/mm² and A/cm² get confused

The numbers 1 and 100 are close enough in a hurry to look like a rounding difference rather than a hundredfold one. A design copied from a 3 A/mm² spec into a 3 A/cm² calculation under-sizes the conductor by 100 times and turns a cool cable into a heating element. The reverse mistake over-sizes by the same factor, which is expensive rather than dangerous but still wrong.

Temperature rise is the other hidden variable. Ampacity figures assume a stated ambient and a stated allowable rise, often 30 °C over 30 °C ambient for cable in free air. The same 8 A/mm² that is fine in a ventilated tray is not fine in a bundled conduit, where derating factors of 0.5 to 0.7 apply.

Derating turns a table value into a real one

Published densities assume a single circuit in free air at 30 °C ambient with a 30 °C rise. Four circuits bundled together apply a factor near 0.8, a conduit adds another 0.7, and a 40 °C plant room takes 0.87 off. Multiply them and a nameplate 8 A/mm² becomes 8 × 0.8 × 0.87 = 5.6 A/mm² before any conduit, or 3.9 inside one. The conversion arithmetic is exact; the engineering is not.

Precision and reporting

Every factor here is exact, so a conversion of 1 A/mm² to A/cm² returns exactly 100 with no floating-point residue. The uncertainty comes from the physical data, not the arithmetic: conductor area is nominal and can be 2–5% under for stranded cable, and current density in a PCB trace is not uniform because copper necks at vias and corners.

Mistakes to avoid

  • Reading 1 A/mm² as 1 A/cm². It is 100 A/cm², so the first figure describes a far cooler conductor.
  • Converting A/dm² straight to A/cm² without dividing by 100. A 4 A/dm² bath is 0.04 A/cm² or 40 mA/cm².
  • Treating 1 oz copper as 1 mm thick. It is 35 µm, 28 times thinner, which is why PCB densities look extreme.
  • Comparing densities measured at different temperature rises: 40 A/mm² at 10 °C rise is not the same duty as 40 A/mm² at 60 °C rise.

Frequently asked questions

How many A/cm² is 1 A/mm²?

Exactly 100, because a square centimetre contains 100 square millimetres. The same density is 1,000,000 A/m² or 100,000 mA/cm².

How do I convert mA/cm² to A/m²?

Multiply by 10. A 20 mA/cm² plating current is 200 A/m², and 5 mA/cm² is 50 A/m².

What is a safe current density for copper wire?

Roughly 3–6 A/mm² for continuous duty in free air, which is 0.03–0.06 A/cm². House wiring runs higher, 8 A/mm² for 20 A on 2.5 mm², because short runs and insulation ratings allow it.

What current density does electroplating use?

Typically 2–10 A/dm², which is 0.02–0.1 A/cm² or 20–100 mA/cm². A dm² is 100 cm², so dividing the A/dm² figure by 100 gives A/cm².

Why does the SI unit A/m² give such big numbers?

Because a square metre is a million square millimetres. A modest 5 A/mm² in a wire is 5,000,000 A/m², so the SI unit is reserved for physics and plasma work rather than wiring.

Is current density constant across a conductor?

No. At DC it is nearly uniform except at corners and constrictions; at high frequency the skin effect pushes current to the surface, so a 10 kHz current in a 10 mm conductor flows in a layer about 0.66 mm deep.

How does 1 oz copper translate to current density?

1 oz copper is 35 µm thick, so a 1 mm wide trace has 0.035 mm². Carrying 2 A gives 2 ÷ 0.035 = 57 A/mm², which is normal for short PCB traces.

What is the difference between ampacity and current density?

Ampacity is the total current a conductor can carry, in amps; current density divides that by area. A 2.5 mm² cable rated 20 A has an ampacity of 20 A and a density of 8 A/mm².

Does the converter round the result?

No. All four factors are exact powers of ten, so 1 A/mm² to A/cm² returns 100.0000 with no rounding error beyond display precision.

Method and sources

Calculation basis

Conversion factors follow the NIST International System of Units (SI); factors that are exact by definition are marked exact.

Last updated: November 19, 2026
Formula & data sources
  • Linear conversion through A/m²: result = value × factor(from) ÷ factor(to).
  • Factors applied: 1 A/cm² = 10000 A/m²; 1 A/mm² = 1000000 A/m²; 1 mA/cm² = 10 A/m².
  • Every factor is an exact decimal SI prefix of the base unit, so no rounded constant is involved.
  • Every factor is an exact definition or an exact decimal SI prefix, so the only error is the floating-point rounding of the arithmetic itself.