R-Value Calculator

Enter the material thickness and conductivity to find its R-value.

=
Quick answer: with the default inputs (3.5 in, 0.27 BTU·in/(hr·ft²·°F)), the r-value is 12.96. Change any input to update the result.
R-value
—

What the R-value number means

For 3.5 in of fiberglass with a conductivity of 0.27, the calculator returns R-12.96. That is the thermal resistance of the material itself, in ft²·hr·°F per BTU: it tells you how many BTUs per hour pass through one square foot for each degree of temperature difference across it. The higher the number, the slower the heat moves.

Why the gauge reads low

The gauge on this page reads Low below 13, Moderate from 13 to 30, and High above 30. A 2x4 cavity lands at the bottom of that range on purpose: R-13 is a cavity fill, not a whole wall. The assembly it sits in, with drywall, sheathing, siding and air films, reaches roughly 15.3. That distinction catches more people than the arithmetic does.

The formula and its units

R=tkR=\frac{t}{k}

Two inputs, one division. t is thickness in inches and k is thermal conductivity in BTU·in/(hr·ft²·°F). The inch in the k unit cancels the inch in the thickness, which is why R comes out ready to use: double the thickness and you double the R, with no extra conversion step.

The k unit is the awkward part. Conductivity is measured per inch of thickness here, not per meter, because that is how US insulation is sold. A material rated k = 0.25 conducts one quarter of a BTU per hour through a one-inch slab, one square foot in area, at one degree of difference. Lower k means better insulation, so k and R pull in opposite directions.

Metric values use RSI, where thickness is in meters and conductivity in W/(m·K). One RSI unit equals 5.678 R, so R-12.96 is RSI 2.28. Divide an R-value by 5.678 to compare it with a European datasheet, and multiply to go the other way.

Worked example: a 2x4 wall cavity

A 2x4 stud is 3.5 in deep, so the cavity holds 3.5 in of insulation. With fiberglass at k = 0.27: R = 3.5 ÷ 0.27 = 12.96. That is the R-13 on the bag, and the bag is right: the labeled number is rounded and measured at a slightly different density, not recalculated from the nominal stud depth.

Switch to mineral wool at k = 0.23 and the same 3.5 in gives 15.22. Switch to closed-cell spray foam at k = 0.154 and it gives 22.73, which is why 3 in of closed-cell foam outperforms a full 3.5-in batt despite leaving half an inch of stud exposed. The thickness did not change; the conductivity did.

Push the same fiberglass into a 3-in furring space and you get 3 ÷ 0.27 = 11.1, not 13. Compression squeezes the air out of the glass, raises the effective k, and the R you paid for disappears into a tighter space. A batt that fits loosely beats one that is forced.

Conductivity and R at 3.5 inches

Materialk (BTU·in/hr·ft²·°F)R at 3.5 in
Polyiso rigid board0.1621.88
Closed-cell spray foam0.15422.73
XPS rigid board0.2017.50
Mineral wool0.2315.22
EPS rigid board0.2514.00
Open-cell spray foam0.2613.46
Fiberglass batt0.2712.96
Pine or fir lumber0.804.38
Brick5.00.70
Glass, single pane7.00.50
Concrete12.00.29

Read the table down the R column, not the k column, and the ranking is what you expect from a building supply aisle. Note where lumber falls: at R-4.38 for 3.5 in, a stud is a thermal bridge that short-circuits about a third of the cavity it frames. A wall of 2x4s at 16 in on center loses roughly 15–20% of its cavity R to the studs alone.

Thickness needed for a target R

Flipping the formula

Flip the formula to plan a build-up: t = R × k. For R-49 at k = 0.27 that is 13.2 in, and 14.7 in if you use loose-fill at k = 0.30. R-38 needs 10.3 in at 0.27, and R-60 needs 16.2 in, which is deeper than any standard stud bay and therefore means blown insulation or a second layer of rigid board.

Batt labels do not track this arithmetic exactly, because manufacturers rate at their own density. A 9.5-in batt is sold as R-30, which implies k = 0.317 rather than 0.27; a 12-in batt is sold as R-38, implying 0.316. Use the label for products and the formula for assemblies, foam thicknesses and anything you are cutting yourself.

How much R-value the code asks for

Climate zoneExample cityCeilingWood wall
1Miami, FLR-30R-13
2Houston, TXR-38R-13
3Atlanta, GAR-49R-20
4New York, NYR-60R-20 + 5
5Chicago, ILR-60R-20 + 5
6Minneapolis, MNR-60R-20 + 5
7Duluth, MNR-60R-20 + 10
8Fairbanks, AKR-60R-20 + 10

These are the 2021 IECC ceiling minimums for wood-frame homes; several states still enforce the 2015 table, which is one step lower from zone 3 upward. Hitting R-60 in a zone 5 attic takes 16.2 in at k = 0.27, so check the joist depth before you price the job: most attics run out of room around 14 in, and the blown insulation then buries the top plate.

What moves the number

  • Thickness is linear: 7 in of the same fiberglass is exactly R-25.93, twice the default
  • Conductivity is inverse: halving k from 0.27 to 0.135 doubles R at the same depth
  • Compression costs R without saving space: 3.5 in squeezed to 3 in drops from 12.96 to 11.1
  • Moisture raises k in fibrous insulation, and a wet batt can lose 30–50% of its rating until it dries
  • Framing is not in the formula at all, and studs at 16 in on center cut whole-wall R by 15–20%
  • Age matters for foam: closed-cell blows with a gas that escapes slowly, so the 20-year R is lower than day one

Where the R-value math misleads

R-values add in series only when the layers are continuous. A wall with R-13 between studs and R-5 of rigid foam on the outside is not R-18 everywhere: it is R-18 at the studs and R-18 in the cavity only if the foam is uninterrupted, which is why foam sheathing is valued out by the fraction of framing it covers.

The other trap is treating R as a comfort guarantee. R-12.96 slows heat flow, it does not stop air. A 3.5-in wall with a 1/8-in gap at the sill plate leaks more heat on a windy 15 °F day than the difference between R-13 and R-15 ever will. Air-seal first, then add R.

  • Whole-wall R is always lower than cavity R, by 15–20% with standard framing
  • A radiant barrier is not an R-value product and cannot be added as one
  • R-value is tested at a fixed mean temperature, so performance shifts at very cold surface temperatures
  • Two layers of R-13 with staggered joints beat one layer of R-26 board at the same total thickness

Frequently asked questions

What R-value do I need for my attic?

Zone 1 asks for R-30, zones 2 to 3 for R-38 to R-49, and zones 4 to 8 for R-60 under the 2021 IECC. At k = 0.27 that R-49 is 13.2 in deep and R-60 is 16.2 in.

How do I calculate R-value from thickness?

Divide thickness in inches by conductivity. A 3.5-in batt at k = 0.27 is 3.5 ÷ 0.27 = 12.96. Two inches of closed-cell foam at k = 0.154 is 12.99.

What is the R-value of a 2x6 wall?

A 2x6 cavity is 5.5 in deep, so fiberglass at k = 0.27 gives 5.5 ÷ 0.27 = 20.37, sold as R-21. The full assembly, with drywall and sheathing, lands near R-23.

Is R-13 enough for an exterior wall?

Only in zones 1 and 2. Zones 3 and up require R-20 or R-20 plus 5 of continuous sheathing, because the studs cut the cavity value by 15–20% before any air leaks are counted.

Does compressing insulation lower its R-value?

Yes. An R-13 batt forced into 3 in of space becomes 3 ÷ 0.27 = 11.1, a loss of about 15%. Buy the depth you have rather than squeezing a thicker batt into it.

How many inches of insulation do I need for R-49?

13.2 in of fiberglass at k = 0.27, or 14.7 in of loose-fill at k = 0.30. Blown cellulose at k = 0.28 needs 13.7 in for the same target.

What is the difference between R-value and RSI?

RSI is the metric version of the same idea, in m²·K/W. One RSI unit is 5.678 R, so R-12.96 equals RSI 2.28 and R-60 equals RSI 10.57.

Do two layers of insulation add up?

Yes, if they stay full thickness. Two 3.5-in layers of fiberglass at k = 0.27 give 25.93, exactly double one layer. Compress either layer and the total drops below the sum.

Is a higher R-value always better?

For heat flow, yes, but the returns flatten. Going from R-13 to R-26 halves conduction through the cavity; going from R-40 to R-53 cuts it by a quarter for the same added inches. Air sealing and window U-factor usually pay back sooner at that point.

Method and sources

Calculation basis

Cost ranges reflect 2026 U.S. national averages for materials and labor; regional pricing varies, so use results as a planning baseline and confirm with local quotes.

Last updated: November 17, 2026
Formula & data sources
  • R-value = thickness ÷ thermal conductivity (k).