Generator Size Calculator
Enter your running and starting wattage to find the recommended generator size.
What the number means
The tool returns peak load, recommended watts and the recommended generator size in kW. At the defaults of 3,000 running watts, 1,500 watts of surge and a 20% margin, the peak is 4,500 W, the recommendation is 5,400 W and the unit to shop for is 5.4 kW. Generators are sold in fixed sizes, so 5.4 kW means a 5,500 W model rather than a 5,000 W one.
How the formula works
Running watts is the steady draw of everything you switch on at once. Starting surge is the extra draw a motor pulls for one to three seconds as it comes up to speed: a refrigerator running at 600 W can pull 1,800 W at startup, so it contributes 1,200 W of surge beyond its running figure.
Enter the surge as the excess, not the total. If you type the 1,800 W startup figure into a 600 W running load, you count that refrigerator twice and oversize the generator by 600 W. The 20% margin then covers the small loads people forget, the fuel-energy conversion losses and the fact that a generator running near its rating overheats and shortens its own life.
Worked example: an essentials panel
A typical outage list adds up like this: refrigerator 600 W, furnace fan 600 W, sump pump 800 W, freezer 400 W, lights 300 W and a TV with router 300 W. That is 3,000 W running. Two of those loads surge: the refrigerator by 1,200 W and the sump pump by 300 W, for 1,500 W of surge.
Running plus surge is 4,500 W, times 1.20 is 5,400 W, or 5.4 kW. A 5,500 W portable covers this panel with 100 W of headroom, and a 7,500 W unit covers it comfortably while leaving room for a coffee maker or a space heater.
2026 appliance wattage reference
| Load | Running W | Starting W |
|---|---|---|
| Refrigerator, 18 cu ft | 600 | 1,800 |
| Chest freezer | 400 | 1,200 |
| Furnace fan, gas | 600 | 1,000 |
| Sump pump, 1/3 hp | 800 | 1,100 |
| Well pump, 1/2 hp | 1,000 | 2,000 |
| Window AC, 10,000 BTU | 1,200 | 2,000 |
| Microwave | 1,000 | 1,000 |
| LED lighting, whole house | 300 | 300 |
| Garage door opener | 300 | 600 |
Motor loads are the ones that matter. Resistive loads like lights, a microwave or a space heater have no surge at all, which is why a 1,500 W space heater is easy to run and a 1,000 W well pump is not: the pump’s 2,000 W startup is what forces the next size up.
What each generator size actually runs
- 2,200 W inverter, $400–$700: fridge, lights, router, phone charging, no heat
- 3,500 W portable, $500–$900: the essentials panel above minus the furnace fan
- 5,500 W portable, $700–$1,200: the full 3,000 W panel with room for a microwave
- 7,500 W portable, $1,000–$1,800: essentials plus a window AC or a space heater
- 10–14 kW standby, $3,000–$8,000 installed: most of a house with load management
- 20–26 kW standby, $8,000–$15,000 installed: whole house including central AC
Portable prices above are the unit alone. Add a 30 A inlet box and cord at $150–$400, or a transfer switch at $400–$900 plus $500–$1,200 to install it. A standby generator also needs a concrete pad, a fuel connection and a permit, which is why its installed price runs two to three times the unit price.
Fuel type changes the real output
A dual-fuel portable rated 5,500 W on gasoline typically makes about 4,950 W on propane, a 10% derate, because propane carries less energy per unit volume through the same carburetor. Derate another 3–4% per 1,000 ft of elevation above sea level for either fuel.
Runtime follows the tank and the load. A 5,500 W unit at half load burns roughly 0.5 gal an hour, so a 6 gal tank lasts about 12 hours. A 20 lb propane cylinder holds 4.7 gal and runs the same load 8–9 hours. A natural gas standby never runs out, which is the main reason people pay for one.
Why a 5,400 W recommendation is not a 5,400 W generator
Generator labels carry two numbers: running watts and surge watts. A 5,500 W model usually surges to 6,875 W for a few seconds. Size on the running number and check that the surge rating clears your calculated peak, because a unit whose running rating matches your peak has no headroom left for the next motor start.
Connection, carbon monoxide and code
Backfeeding is not a shortcut
Never backfeed a house through a dryer outlet. A suicide cord sends 240 V onto the utility lines and can kill a lineman working a mile away. The legal paths are a transfer switch at $400–$900 installed or a breaker interlock kit at $150–$400, both of which force the main breaker off before the generator can energize the panel.
Run a portable outdoors, at least 20 ft from doors, windows and vents, with the exhaust pointing away. Carbon monoxide kills people every storm season because a generator in a garage or under a carport seems close enough to watch. A $30 battery CO alarm in the hallway is the cheapest safety item in the whole setup.
Mistakes that size a generator wrong
- Adding every nameplate in the house instead of what runs at once
- Forgetting the well pump, which is often the single largest surge on the panel
- Entering total starting watts rather than the surge above running
- Skipping the transfer switch and running extension cords through a window for weeks
- Buying an open-frame unit for electronics, which can carry 15–20% total harmonic distortion
- Running a conventional generator below 30% load for days, which glazes the cylinder
If the panel includes a modem, a TV and a furnace control board, buy an inverter generator. Total harmonic distortion under 3% protects electronics that a conventional unit can damage, and the eco-throttle cuts fuel use by a third at light load, which matters when the only thing running overnight is a fridge and a fan.
Frequently asked questions
What size generator do I need for my house?
Add the running watts of everything you need at once, add the motor surges, then add 20%. The 3,000 W essentials panel here comes to 5,400 W, so a 5,500 W portable or a 10 kW standby.
How many watts does a refrigerator need to start?
About 1,800 W for the first few seconds, against 600 W while running. That 1,200 W of surge is often what pushes a plan from a 3,500 W to a 5,500 W generator.
What is the difference between running and starting watts?
Running watts is the steady draw. Starting watts is the brief surge a motor pulls to come up to speed, typically 2–3 times its running figure for a compressor or pump.
Can a 5,000 watt generator run a house?
It runs an essentials panel: fridge, furnace fan, sump pump, freezer and lights at 3,000 W, with 2,000 W left for small appliances. It will not run central AC, a well pump and a water heater together.
What size generator runs a whole house?
Twenty to twenty-six kW for a house with central AC, or 10–14 kW with load management that sheds the big loads automatically. Installed cost runs $8,000–$15,000 for the larger units.
How long will a generator run on a tank of gas?
About 12 hours on a 6 gal tank at half load, since a 5,500 W unit burns roughly 0.5 gal an hour. On a 20 lb propane cylinder, expect 8–9 hours because propane delivers about 10% less output.
Do I need a transfer switch?
Yes for any connection to house wiring. A transfer switch at $400–$900 installed or an interlock kit at $150–$400 keeps generator power off the utility lines. Backfeeding through an outlet is illegal and lethal to line workers.
How far should a generator be from the house?
At least 20 ft from doors, windows and air intakes, with exhaust pointing away. Carbon monoxide from a unit in a garage or under a carport kills people every storm season.
Is an inverter generator worth the extra cost?
For electronics, yes. Inverter models hold total harmonic distortion under 3%, against 15–20% for conventional units, and eco-throttle cuts fuel use by about a third at light load.
Does a generator lose power at altitude?
Yes, about 3–4% per 1,000 ft above sea level. At 5,000 ft a 5,500 W unit delivers roughly 4,600 W, so size up if you live high.
Method and sources
- Generator sizing: running plus starting wattage with 20% margin; typical home backup 5,000-7,500 W.