# Thermal Conductance Converter

Convert thermal conductance between W/K and BTU/(h·°F).

## Quick answer

**Thermal Conductance Converter** — convert between W/K, BTU/(h·°F) and more.

## Default calculation

Values computed by this calculator at exactly the default inputs listed below.

### Inputs (defaults)

| Input | Value | Unit |
| --- | --- | --- |
| Value | 1 |  |
| From | W/K |  |
| To | BTU/hF |  |

### Outputs at these defaults

| Output | Value | Unit |
| --- | --- | --- |
| Result | 1.89563 |  |

## Formula

```text
result = value × factor(from) ÷ factor(to), with factors in W/K: W/K = 1, BTU/(h&middot;&deg;F) = 0.5275279
```

## Inputs

| Variable | Type | Unit | Default |
| --- | --- | --- | --- |
| Value | number |  | 1 |
| From | select |  | W/K |
| To | select |  | BTU/hF |

## Outputs

| Result | Format |
| --- | --- |
| Result | primary |
| Result | unit |

## How it works

### What thermal conductance is

Thermal conductance is heat flow per degree of temperature difference across a whole component: watts per kelvin, W/K. It is what you get when you multiply a U-value by the area it covers, and it is the number that tells you how many watts a window, wall or heat sink passes for each degree you push across it. At the defaults, **1 W/K** converts to **1.896 BTU/(h&middot;&deg;F)**.

Two units cover most work: W/K in SI, and BTU per hour per degree Fahrenheit in US building and HVAC practice. The conversion is a single ratio: *result = value × factor(from) ÷ factor(to)*, with W/K as the base.

### Why 1 W/K equals 1.896 BTU/(h&middot;&deg;F)

Two conversions stack. One watt is 3.412142 BTU/h, and a one kelvin difference is 1.8 degrees Fahrenheit. Conductance per degree Fahrenheit is therefore 3.412142 ÷ 1.8 = **1.8956 BTU/(h&middot;&deg;F)**. Note that the number gets bigger, not smaller, when you move to Fahrenheit: the same heat flow is being divided by a larger temperature number, so each Fahrenheit degree carries less heat than a kelvin.

The reverse factor, 0.5275279, is the number of watts per kelvin in one BTU per hour per degree Fahrenheit. It is simply the reciprocal: 1 ÷ 1.8956 = 0.5275. A 10,000 BTU/(h&middot;&deg;F) whole-house conductance is 5,275 W/K, and a 1,000 W/K wall is 1,896 BTU/(h&middot;&deg;F).

#### Conductance, conductivity and resistance are three units

Thermal conductivity is W/(m&middot;K) and describes a material. Thermal conductance is W/K and describes a component: conductivity multiplied by area and divided by thickness. Thermal resistance is K/W, the reciprocal of conductance, and this converter does not output it — a 2 W/K component has a resistance of 0.5 K/W. Getting these three mixed up is the single most common error in this family, because all three are written with W and K in some order.

### Worked example at the default settings

Convert 1 W/K to BTU/(h&middot;&deg;F): 1 × 1 ÷ 0.5275279 = **1.8956 BTU/(h&middot;&deg;F)**. In conductance terms, one watt flows for every kelvin of difference, which is 3.41 BTU/h per 1.8 &deg;F, or 1.896 BTU/h per single &deg;F.

Apply it to a building. A 1.5 m² window with a U-value of 1.4 W/(m²&middot;K) — a good double-glazed unit — has a conductance of 1.5 × 1.4 = **2.1 W/K**, which is 3.98 BTU/(h&middot;&deg;F). On a 20 &deg;C day-night difference it leaks 42 W, or 143 BTU/h. A whole house of 200 m² at an average U of 0.3 W/(m²&middot;K) reaches 60 W/K, or 113.7 BTU/(h&middot;&deg;F).

### Conductance values in both units

| Component | W/K | BTU/(h&middot;&deg;F) |
| --- | --- | --- |
| 1 m² single glazing (U 5.8) | 5.8 | 11.0 |
| 1.5 m² double glazing (U 1.4) | 2.1 | 4.0 |
| 100 m² wall at U 0.3 | 30 | 56.9 |
| 200 m² house at U 0.3 | 60 | 113.7 |
| Heat sink, 1.5 &deg;C/W | 0.67 | 1.26 |
| 3-ton AC at 20 &deg;F split | 949 | 1,800 |

The last row shows how the two systems meet in practice: a 36,000 BTU/h air conditioner working across a 20 &deg;F indoor-outdoor difference implies 36,000 ÷ 20 = 1,800 BTU/(h&middot;&deg;F), which is 949 W/K. A European engineer sizing the same house would start from 949 W/K and a 11 K difference, getting 10.4 kW of heat load — the same building, described in two sets of units.

### Where conductance numbers come from in buildings

- Assemblies: add the conductance of each layer in series as resistances, not conductances. A wall of R-13 insulation plus 12 mm gypsum ends near 30 W/K per 100 m², or 56.9 BTU/(h&middot;&deg;F).
- Windows: a 1.5 m² unit at U 1.4 is 2.1 W/K; at U 0.8 (triple glazing) it drops to 1.2 W/K, a 43% cut for that opening.
- Thermal bridging: steel studs can double the conductance of the insulated field, so a wall calculated at 30 W/K may measure 55 W/K on site.
- Air leakage is separate: a 50 Pa blower-door result in ACH50 does not convert to W/K without a heat-capacity term, and mixing the two understates the real load.

The series rule is the one to internalise: conductances add only in parallel. Two identical 2 W/K windows side by side make 4 W/K, but two layers of material stacked through the thickness each of 2 W/K give 1 W/K, because their resistances of 0.5 K/W add. Adding conductances in series is the error that makes a well-insulated wall look three times leakier than it is.

#### Electronics cooling uses the same unit backwards

Heat sink data sheets quote thermal resistance in &deg;C/W, so a 1.5 &deg;C/W sink is 0.667 W/K, or 1.26 BTU/(h&middot;&deg;F). A 30 W chip on that sink runs 45 &deg;C above ambient, which is 1.5 × 30. Converting the sink to conductance first makes the arithmetic a multiplication instead of a division and removes the usual sign and reciprocal mistakes.

### Precision

The 1.8956 factor rests on two exact definitions, 3.412142 BTU/h per watt and 1.8 &deg;F per K, so a conversion is accurate to the last digit shown. The uncertainty is in the input: a calculated U-value assumes still air films and clean surfaces, and wind or solar gain can move the effective conductance by 20–30%. Round results to two significant figures, as the table does.

### Mistakes worth avoiding

- Multiplying by 1.896 when going from BTU/(h&middot;&deg;F) to W/K. The direction is multiply by 0.5275, so 1,800 BTU/(h&middot;&deg;F) is 949 W/K.
- Treating W/(m²&middot;K) as W/K. The first is a U-value per unit area; the second already includes area, so a 2 m² window at U 1.5 is 3 W/K, not 1.5.
- Adding conductances in series. Use resistances, add them, then invert.
- Confusing K/W with W/K by reading the letters rather than the arithmetic: 0.5 K/W is 2 W/K, not 0.5 W/K.

## FAQ

### How many BTU/(h&middot;&deg;F) is 1 W/K?

1.8956. One watt is 3.412142 BTU/h and one kelvin is 1.8 &deg;F, so 3.412142 ÷ 1.8 = 1.8956.

### How do I convert BTU/(h&middot;&deg;F) to W/K?

Multiply by 0.5275. A 1,800 BTU/(h&middot;&deg;F) house conductance is 949 W/K, and 10,000 BTU/(h&middot;&deg;F) is 5,275 W/K.

### Is thermal conductance the same as thermal conductivity?

No. Conductivity is W/(m&middot;K) for a material; conductance is W/K for a component, equal to conductivity times area divided by thickness. A 50 mm panel of 0.03 W/(m&middot;K) insulation over 1 m² has a conductance of 0.6 W/K.

### How do I get conductance from a U-value?

Multiply by area. A U-value of 1.4 W/(m²&middot;K) over 1.5 m² gives 2.1 W/K, which is 3.98 BTU/(h&middot;&deg;F).

### What is 60 W/K in BTU?

113.7 BTU/(h&middot;&deg;F), from 60 × 1.8956. That is a typical whole-house conductance for 200 m² at an average U of 0.3.

### How many watts does a 2 W/K window leak at 20 K difference?

40 W, which is 136 BTU/h. Double the difference to 40 K and it leaks 80 W.

### How do I convert degrees C per watt to W/K?

Take the reciprocal. A heat sink rated 1.5 &deg;C/W is 1 ÷ 1.5 = 0.667 W/K, or 1.26 BTU/(h&middot;&deg;F).

### What does a 3-ton air conditioner imply in W/K?

36,000 BTU/h across a 20 &deg;F split is 1,800 BTU/(h&middot;&deg;F), or 949 W/K. Across 11 K that is 10.4 kW of heat load.

### Why does 1 W/K become a larger number in BTU?

Because a Fahrenheit degree is smaller than a kelvin, so more of them are needed for the same temperature difference. The flow per degree therefore looks larger, at 1.8956 BTU/h per &deg;F.

## Method and sources

Methodology: Conversion factors follow the NIST International System of Units (SI); factors that are exact by definition are marked exact.

Last updated: 2026-11-19.
- Linear conversion through W/K: result = value × factor(from) ÷ factor(to).
- Factors applied: 1 BTU/(h·°F) = 0.5275279 W/K.
- The BTU per hour-°F uses the International Table BTU (1055.05585262 J), 3600 seconds per hour and 5/9 kelvin per Fahrenheit degree; the stored factor is rounded.
- The SI prefixes are exact; the BTU/(h·°F) factor is stored as a rounded decimal, the largest deviation being 5.0e−6% relative. A result carries that rounding on top of floating-point arithmetic.