# Heat Loss Calculator

Estimate heat loss in BTU per hour through a wall, window or roof from its area, U-value and temperature difference.

## Quick answer

**Quick answer:** with the default inputs (1,000 sq ft, 0.15 BTU/h·ft²·°F, 30 °F), the heat loss is **4,500**. Change any input to update the result.

## Default calculation

Values computed by this calculator at exactly the default inputs listed below.

### Inputs (defaults)

| Input | Value | Unit |
| --- | --- | --- |
| Surface area | 1000 | sq ft |
| U-value | 0.15 | BTU/h·ft²·°F |
| Temperature difference | 30 | °F |

### Outputs at these defaults

| Output | Value | Unit |
| --- | --- | --- |
| Heat loss | 4500 |  |

## Formula

```text
heat loss = area × U-value × temperature difference
```

## Inputs

| Variable | Type | Unit | Default |
| --- | --- | --- | --- |
| Surface area | number | sq ft | 1000 |
| U-value | number | BTU/h·ft²·°F | 0.15 |
| Temperature difference | number | °F | 30 |

## Outputs

| Result | Format |
| --- | --- |
| Heat loss | primary |
| Heat loss | unit |

## How it works

### What this calculator does

Enter a surface area, its U-value and the indoor–outdoor temperature difference, and the calculator returns the conductive heat loss in **BTU per hour**. At the defaults — 1,000 sq ft of surface with a U-value of **0.15** and a **30&deg;F** temperature difference — heat loss is **4,500 BTU/h**. This is the steady-state number for one surface; a whole house is the sum of its walls, windows, roof and floor, each with its own U-value.

### How the formula works

The U-value measures how fast heat passes through one square foot of the surface for each degree of difference between the two sides, in BTU/h&middot;ft²&middot;&deg;F. Low U means good insulation: an uninsulated wall runs near **0.30**, a modern insulated wall near **0.06–0.10**. The &Delta;T term is the driving force — heat loss scales linearly with temperature difference, so doubling a 30&deg;F gap to 60&deg;F exactly doubles the loss.

The linearity is what makes the formula useful for planning. The 4,500 BTU/h default is what that surface loses on a day 30&deg;F colder outside than in; on the coldest design day, say 55&deg;F of difference, the same surface loses 7,500 BTU/h. Sizing equipment against your local design temperature rather than an average winter day is standard engineering practice, and the calculator lets you sweep &Delta;T to compare both.

### Worked example at the defaults

One thousand square feet of surface at U = 0.15 with &Delta;T = 30&deg;F: 1,000 × 0.15 × 30 = **4,500 BTU/h**. In watts that is about 1,319 W of continuous loss, and over a full 24-hour day the surface sheds 108,000 BTU — close to one therm of natural gas — which at $1.50–$2.00 per therm is roughly $1.60–$2.20 a day for this single surface alone.

Now swap the U-value. The same 1,000 sq ft at an insulated-wall U of 0.08 loses 2,400 BTU/h — a 47% cut — and costs about $1.10 a day under the same conditions. Over a 120-day heating season, the difference between U = 0.15 and U = 0.08 is on the order of $60–$130 for this one surface, before you count the second and third surfaces of the house.

### Typical U-values by surface

| Surface | Typical U-value |
| --- | --- |
| Single-pane window | 0.9–1.1 |
| Double-pane window | 0.45–0.55 |
| Double-pane, low-e coating | 0.25–0.35 |
| Uninsulated 2×4 wall | ≈0.30 |
| Wall with R-13 cavity insulation | ≈0.08–0.10 |
| Wall with R-19 cavity insulation | ≈0.06–0.07 |
| Attic with R-38 insulation | ≈0.03 |

#### The U-value and R-value relationship

U and R are reciprocals: U = 1 ÷ R. An R-13 wall cavity is U ≈ 0.077 by the label, but real assemblies include studs, plates and corner framing that bridge the insulation, so the whole-wall U lands nearer 0.09–0.10. Windows show the same asymmetry — a window&rsquo;s center-of-glass U is always better than its whole-unit U because the frame leaks more than the glass. Use whole-assembly values in the calculator; they are what your energy bill actually experiences.

### What moves the number

- Insulation level: going from an uninsulated wall (0.30) to R-13 (0.10) cuts heat loss by two-thirds for the same wall
- Temperature difference: loss is linear in &Delta;T, so a 60&deg;F design day doubles a 30&deg;F day
- Area: each 100 sq ft at U = 0.15 adds 450 BTU/h per 30&deg;F of difference
- Windows: at U ≈ 0.5 a 100 sq ft window loses about five times what the same area of insulated wall does
- Thermal bridges: studs and uncut rim joists add 15–25% over the cavity-only estimate

### Conduction is only half the story

The formula covers conduction through solid surfaces. Air leakage — infiltration through gaps, penetrations and leaky ducts — typically adds another 25–40% to a leaky house&rsquo;s heating load, and ventilation brings outside air in by design. A blower-door test measures infiltration directly; without one, a common planning step is to add 20–30% on top of the summed conduction losses before sizing equipment.

#### The infiltration allowance

That is also why sealing beats adding insulation in specific places. Weatherstripping and sealing a rim joist or attic hatch costs tens of dollars and removes loss that no amount of batt insulation touches, because moving air carries heat away faster than conduction through the same gap.

### From heat loss to equipment size

To size a heater, sum the heat loss of every exterior surface at your local design temperature, add the infiltration allowance, and you have the load in BTU/h the equipment must meet. A furnace rated 60,000 BTU/h at 95% efficiency delivers 57,000 BTU/h into the house, which must cover the summed load with a modest margin. Over-sizing a furnace by more than about 25–30% causes short cycling — frequent on-off cycles that waste fuel and wear parts — so resist the temptation to round up aggressively.

For heat pumps the same arithmetic sets the balance point: the outdoor temperature where building heat loss equals heat pump output. Below it, supplemental resistance heat takes over — and resistance heat costs two to three times more per BTU, which is why envelope work such as insulation and air sealing is usually the cheapest capacity you can buy.

### Common mistakes in heat-loss estimates

- Using label R-values instead of whole-assembly U-values, overstating performance by 15–25%
- Measuring wall area including window openings at the wall U-value — windows need their own, much higher U
- Ignoring the slab or basement walls, which lose heat year-round in cold climates
- Applying average winter &Delta;T instead of the design temperature, undersizing equipment on the coldest nights
- Forgetting that conduction is only part of the load and skipping the infiltration allowance

## FAQ

### What is a U-value?

The rate heat passes through a surface, in BTU per hour per square foot per degree of temperature difference. Lower is better: an uninsulated wall runs about 0.30 and an R-13 insulated wall about 0.09.

### How do I calculate heat loss through a wall?

Multiply area by U-value by the temperature difference. A 1,000 sq ft wall at U = 0.15 with a 30&deg;F gap loses 1,000 × 0.15 × 30 = 4,500 BTU/h.

### How many BTU is my house losing?

Sum each surface: its area times its U-value times your design temperature difference. A typical 1,500 sq ft home lands in the 30,000–60,000 BTU/h range on a design day, plus a 20–30% infiltration allowance.

### How do I convert heat loss to watts?

Multiply BTU/h by 0.293. The default 4,500 BTU/h is about 1,319 watts of continuous heat flow, and a 24-hour day at that rate sheds 108,000 BTU — roughly one therm of gas.

### What U-value should I aim for in a wall?

R-13 cavity insulation puts a whole 2×4 wall near 0.09–0.10; R-19 in a 2×6 frame reaches about 0.06–0.07. Cold climates favor the thicker assembly, where each step down in U cuts loss proportionally.

### How much does insulating a wall save?

Going from uninsulated (U = 0.30) to R-13 (U ≈ 0.10) cuts conductive loss by two-thirds. On the default surface that is 4,500 down to 1,500 BTU/h per 30&deg;F of difference, worth roughly $60–$130 per season per 1,000 sq ft at typical gas prices.

### Does this include air leaks?

No — the formula covers conduction only. Air infiltration typically adds 25–40% in a leaky house, so add a 20–30% allowance before sizing equipment, or measure it with a blower-door test.

### What temperature difference should I use?

Your local design temperature — the near-coldest normal winter condition, often 15–25&deg;F below indoor setpoint. Using average winter temperatures instead undersizes equipment exactly on the nights it matters.

### Why does a window lose more heat than a wall?

A double-pane window runs U ≈ 0.5 versus about 0.09 for an insulated wall, so the same 100 sq ft of window loses roughly five times the heat. Low-e coatings drop the window to 0.25–0.35, halving the penalty.

### Should I oversize my heater to be safe?

Beyond about 25–30%, no. Oversized furnaces short cycle, wasting fuel and wearing parts, while oversized heat pumps lose efficiency and lean on expensive resistance heat. Size to the calculated load plus the infiltration allowance.

## Method and sources

Methodology: Cost ranges reflect 2026 U.S. national averages for materials and labor; regional pricing varies, so use results as a planning baseline and confirm with local quotes.

Last updated: 2026-11-17.
- Heat loss = area × U-value × temperature difference; U-value in BTU/h·ft²·°F.