# AWG to mm Converter

Convert American Wire Gauge (AWG) sizes to wire diameter in millimetres and inches, or back to the nearest AWG. Free and instant.

## Quick answer

**Quick answer:** 12 AWG = **2.05 mm** Enter a value and units to convert any amount instantly.

## Default calculation

Values computed by this calculator at exactly the default inputs listed below.

### Inputs (defaults)

| Input | Value | Unit |
| --- | --- | --- |
| Value | 12 |  |
| From | AWG |  |
| To | mm |  |

### Outputs at these defaults

| Output | Value | Unit |
| --- | --- | --- |
| Result | 2.05253 |  |

## Formula

```text
d (in) = 0.005 × 92^(36 − n) / 39  &middot;  d (mm) = d (in) × 25.4
```

## Inputs

| Variable | Type | Unit | Default |
| --- | --- | --- | --- |
| Value | number |  | 12 |
| From | select |  | AWG |
| To | select |  | mm |

## Outputs

| Result | Format |
| --- | --- |
| Result | primary |
| Result | unit |

## How it works

### What AWG measures

American Wire Gauge is a numbering system for the diameter of round conductors. Every gauge number is tied to a single diameter, so AWG 12 means 2.05 mm of bare copper whether you are looking at a house circuit or a loudspeaker cable. This converter goes from a gauge number to millimetres or inches, and back from a measured diameter to the nearest gauge.

### The formula

The scale is geometric, not arithmetic. Gauge 36 is defined as 0.005 in and gauge 0 as 0.325 in, and the 36 steps between them are spaced so that the ratio of successive diameters is constant. That constant is 92^1/39 = 1.1229, which is why every six steps multiply the diameter by 92^6/39 = 2.005 — almost exactly double.

Working backwards, the tool inverts the same expression: n = 36 − 39 × log(d ÷ 0.005) ÷ log(92), then rounds to the nearest whole gauge. A measured 2.05 mm therefore returns 12, and a 2.06 mm measurement also returns 12 because gauges are integers in this range.

The two reference points come from the nineteenth-century Brown and Sharpe gauge: 36 gauge was the finest wire the mills could draw at 0.005 in, and 0 was the largest at 0.325 in. Fitting a constant ratio between known endpoints was easier to manufacture than a table, and the resulting scale has survived every subsequent standardisation because it is self-consistent.

#### Where the number stops being useful

- Material. AWG describes the diameter, so an aluminium conductor is the same size and carries about two gauges less current than the copper equivalent.
- Stranding and plating. Tinned, stranded or compact-stranded cable keeps the nominal area, and the diameter of the bundle can exceed the equivalent solid wire.
- Insulation thickness. A 12 AWG conductor with heavy rubber insulation does not fit the same conduit as the same conductor with thin thermoplastic, which is a conduit-fill question rather than a gauge one.

### Worked example at 12 AWG

Take the default. The exponent is (36 − 12) ÷ 39 = 0.6154, so 92^0.6154 = 16.16 and the diameter is 0.005 × 16.16 = 0.0808 in. Multiply by 25.4 and you get **2.05 mm**, which is the number printed on every 20-amp circuit cable in North America.

Area follows from the diameter: &pi; ÷ 4 × 2.053² = **3.31 mm²**. That cross-section is what sets resistance, and 3.31 mm² of copper carries about 5.2 &Omega; per kilometre, so 30 m of it loses 3.1 V at 20 A in each direction, 6.2 V over the round trip — right at the 5 percent limit that wiring codes work to.

### Common sizes and what they carry

| AWG | Diameter (mm) | Area (mm²) | Typical use |
| --- | --- | --- | --- |
| 0 | 8.25 | 53.5 | service entrance, 125 A |
| 4 | 5.19 | 21.2 | range or subpanel feeder |
| 6 | 4.11 | 13.3 | 60 A circuit, EV charger |
| 8 | 3.26 | 8.37 | 40 A circuit, large appliance |
| 10 | 2.59 | 5.26 | 30 A dryer or AC circuit |
| 12 | 2.05 | 3.31 | 20 A general receptacle circuit |
| 14 | 1.63 | 2.08 | 15 A lighting circuit |
| 18 | 1.02 | 0.823 | lamp cord, low-voltage runs |
| 24 | 0.51 | 0.205 | network and signal cable |

The table shows the rule at work: 12 to 6 is six steps and the diameter doubles from 2.05 to 4.11 mm, while the area quadruples from 3.31 to 13.3 mm². Three steps double the area instead — 12 AWG at 3.31 mm² to 9 AWG at 6.63 mm² — which is a handy check when a spec quotes area rather than gauge.

### Diameter is not ampacity

#### Why the same wire carries different currents

Ampacity depends on insulation temperature rating, bundling, ambient temperature and conduit fill, not just the copper. The same AWG 12 conductor is rated 20 A at 60&deg;C insulation and 25 A at 75&deg;C, and a bundle of ten current-carrying conductors in one conduit gets derated by 50 percent. The diameter is fixed by the gauge; the current is not.

This is why a converter is the right first step and never the last one. Once you know the diameter and area, the code table decides the breaker. Buying 12 AWG for a 30 A circuit because 2.05 mm looks substantial is the classic error, and it ends with a warm cable inside a wall.

### Metric equivalents

#### Matching mm&sup2; cable to AWG

European cable is sold by cross-section, so a 2.5 mm² conductor has a diameter of 1.78 mm — between AWG 13 at 2.63 mm² and AWG 14 at 2.08 mm², nearest to 13. It is not the same as 12 AWG, which is 3.31 mm² and 32 percent larger. A 1.5 mm² cable is 1.38 mm across, close to AWG 16 at 1.31 mm².

The mismatch matters when equipment arrives with a metric gland or a US-style terminal. A 2.5 mm² cable is fine in a 20 A European circuit and undersized against a 20 A US breaker that assumes 12 AWG, so a swap needs the ampacity table of the destination country rather than a diameter conversion alone.

### Mistakes that survive a quick look

- Assuming a bigger number means a thicker wire. It is the reverse: 18 AWG is 1.02 mm and 8 AWG is 3.26 mm.
- Entering 1/0, 2/0 or 4/0 as 10, 20 or 40. Those aught sizes are larger than 0 and outside this tool&rsquo;s 0–40 range.
- Confusing diameter with area when comparing to metric cable. 12 AWG is 2.05 mm across but 3.31 mm² in section.
- Sizing by looks. A 2.05 mm conductor and a 2.08 mm conductor are AWG 12 and 14 respectively — 0.03 mm apart, and 30 percent apart in area.

Rounding also hides the difference between neighbours. Gauges near 12 differ by about 12 percent in diameter per step, which is 25 percent in area and 25 percent in ampacity. That is why a conversion to two decimals is enough to identify a gauge and never enough to justify substituting one.

## FAQ

### What is 12 AWG wire in millimetres?

2.05 mm in diameter, which is 0.0808 in and 3.31 mm² in cross-section.

### Is a lower AWG number thicker?

Yes. AWG 8 is 3.26 mm and AWG 18 is 1.02 mm, so the diameter falls as the number rises.

### How do I convert mm to AWG?

Use n = 36 − 39 log(d ÷ 0.005) ÷ log(92) and round to a whole number. A 2.05 mm conductor returns 12; a 1.63 mm conductor returns 14.

### What is 10 AWG in millimetres?

2.59 mm, or 5.26 mm². That is the usual size for a 30 A dryer or air-conditioner circuit.

### How much does 6 AWG carry?

4.11 mm across, 13.3 mm², and typically 55 A at 60&deg;C insulation. Ampacity rises further at 75&deg;C and falls when cables are bundled.

### Why does every 6 gauges double the diameter?

Because 92^6/39 = 2.005, a consequence of fitting 36 constant-ratio steps between 0.005 in and 0.325 in.

### What is 2.5 mm&sup2; cable in AWG?

About AWG 13, since 2.5 mm² corresponds to 1.78 mm diameter and AWG 13 is 2.63 mm². It is not a substitute for 12 AWG at 3.31 mm².

### What about 1/0 and 2/0 wire?

Those are sizes larger than 0, pronounced one-aught and two-aught. They sit outside the 0–40 range this converter accepts, so enter them as their millimetre diameter instead.

### Does AWG apply to stranded wire?

The gauge describes the equivalent solid conductor. A 12 AWG stranded cable has the same total copper area, 3.31 mm², but each strand is much thinner, which makes it flexible without changing ampacity.

## Method and sources

Methodology: Conversion factors follow the NIST International System of Units (SI); factors that are exact by definition are marked exact.

Last updated: 2026-11-17.
- ASTM B258: standard nominal diameters of AWG wire.
- AWG diameter formula d = 0.005 in × 92^((36−n)/39).