Tankless Water Heater Calculator
Enter the flow rate and inlet and target temperatures to calculate the required tankless heater capacity.
What the output means
The result is the BTU per hour a tankless heater must burn to raise your incoming water to the target temperature at the flow you asked for, plus the temperature rise that drives it. At the defaults — 5 GPM, 50°F inlet, 120°F target — the rise is 70°F and the requirement is 175,000 BTU/h. That number is a hard floor: a unit rated below it will not deliver 5 GPM at 120°F no matter what the box says.
Where the 500 comes from
Heating a gallon of water by 1°F takes 8.33 BTU, and a gallon weighs 8.33 lb. At a flow of one gallon per minute you heat that mass sixty times an hour, so 8.33 × 60 = 500 BTU per hour for every 1°F of rise. The constant is therefore not a fudge factor: it is pounds per gallon times minutes per hour, rounded. Keep units consistent and the formula holds for any flow and any rise.
Temperature rise is simply target minus inlet. An inlet of 50°F and a target of 120°F is a 70°F rise. That term is where climate enters: groundwater in the Deep South runs near 67°F and needs only a 53°F rise, while a northern well at 40°F needs 80°F. The same heater therefore delivers about 25–30% more hot water in Miami than in Minneapolis.
Worked example at 5 GPM
Rise: 120 − 50 = 70°F. Demand: 5 × 70 × 500 = 175,000 BTU/h. A standard residential tankless unit tops out at 199,000 BTU/h, so this load fits with about 14% headroom and delivers 199,000 ÷ (70 × 500) = 5.69 GPM at that rise. The calculator asks for the minimum; the unit’s rating tells you what is left over.
Now change one input. Target 140°F instead of 120°F is an 90°F rise, and 5 × 90 × 500 = 225,000 BTU/h, which no single residential unit achieves — you would need to drop to 3.9 GPM or accept 120°F. Drop the flow to 3 GPM at the original 70°F rise and the requirement falls to 105,000 BTU/h, comfortably inside a mid-size unit. Flow and rise trade against each other linearly, and both trade against the unit rating.
GPM delivered at 175,000 BTU/h
| Region | Inlet temp | Rise to 120°F | GPM delivered |
|---|---|---|---|
| Deep South | 67°F | 53°F | 6.6 GPM |
| Moderate | 50°F | 70°F | 5.0 GPM |
| Northern | 40°F | 80°F | 4.4 GPM |
| Cold well | 35°F | 85°F | 4.1 GPM |
This is the table to check before buying. A unit rated 175,000 BTU/h handles two showers and a faucet in Georgia and struggles to run one shower and a dishwasher in Michigan. Buyers who compare only the GPM printed on the spec sheet — usually quoted at a 40–50°F rise — consistently end up with a heater that cannot keep up in February.
Building your GPM budget
- Shower: 2.0–2.5 GPM for a modern head, 4–5 GPM for an older or rain head.
- Bathroom faucet: 1.0–1.5 GPM, and 0.5–1.0 for a low-flow aerator.
- Kitchen faucet: 1.5–2.2 GPM, higher if it is a pull-down sprayer.
- Dishwasher: 1.0–2.0 GPM while filling, then intermittent.
- Washing machine: 2.0–4.0 GPM during fill, the biggest single spike in most homes.
Simultaneous use
Add only the fixtures that actually run at the same time. Two showers plus a bathroom faucet is 5.0–6.5 GPM; a shower plus a dishwasher is 3.0–4.5 GPM. A family of four with two bathrooms rarely exceeds 6 GPM at once, which is why a 199,000 BTU unit covers most homes — but a three-bath house with simultaneous morning use needs 8–9 GPM and either a larger condensing unit or two units in a cascade.
What people get wrong
- Sizing to the spec sheet GPM, which is always quoted at a lower rise than your climate delivers.
- Ignoring the cold-water flush on a washing machine, which pulls full flow for a minute or two.
- Forgetting that 199,000 BTU/h typically needs a 3/4 in gas line, and many homes have 1/2 in at the meter.
- Expecting instant hot water: a tankless unit still has to purge the line, so a 30 ft run is 5–8 seconds of cold.
The gas line is the most expensive surprise. A 199,000 BTU/h appliance draws about 200 cubic feet of gas an hour, which is more than a furnace and a range combined. If the existing run is undersized, upgrading to 3/4 in or 1 in black iron costs $500–$1,500, and that single line item can erase three years of the $100–$200 annual energy savings a tankless unit is credited with.
Condensing versus non-condensing
Condensing units capture latent heat from the exhaust and reach 0.90–0.96 efficiency, but they produce acidic condensate that must be drained and neutralized, and they vent in PVC at $300–$800 for the kit. Non-condensing units run 0.80–0.85, vent in stainless steel, and cost $400–$800 less to buy. In a cold climate, the condensing unit is usually the right call: the higher rise per BTU matters most exactly where the groundwater is coldest.
Do you need a recirculation loop
A recirculation pump at $200–$600 installed removes the cold-water purge but keeps the unit cycling, and a continuously recirculating system can add $150–$400 a year in gas. An on-demand button or motion sensor is the compromise. In a compact house where the farthest fixture is 20 ft away, the wait is 2–3 seconds and the loop is not worth the cost.
Frequently asked questions
How do I size a tankless water heater?
Add the GPM of the fixtures you run at once, subtract the inlet temperature from 120°F, then multiply by 500. Five GPM at a 70°F rise needs 175,000 BTU/h.
What temperature rise do I need?
Target minus inlet. Groundwater at 50°F to a 120°F target is a 70°F rise; at 40°F it is 80°F, which cuts output by about 12% on the same heater.
How many GPM does a tankless water heater deliver?
A 175,000 BTU/h unit gives 5.0 GPM at a 70°F rise, 6.6 GPM at 53°F and 4.1 GPM at 85°F. Always convert the spec sheet rating to your own rise before comparing.
Is 199,000 BTU enough for a whole house?
For most homes, yes: 199,000 ÷ (70 × 500) = 5.69 GPM at a 70°F rise, enough for two showers. A three-bath house with simultaneous morning use needs 8–9 GPM, which requires a larger or cascaded system.
Does a tankless water heater save money?
About $100–$200 a year in gas for a typical family, which is $1,000–$2,000 over its 20-year life. A $500–$1,500 gas line upgrade can wipe out the first several years of that.
Can a tankless heater run two showers at once?
At 2.5 GPM each, two showers need 5 GPM, which is a 70°F rise at 175,000 BTU/h. Add a third fixture and you will exceed a standard 199,000 BTU unit.
What size gas line does a tankless water heater need?
A 199,000 BTU/h unit typically needs 3/4 in black iron, and 1 in if the run exceeds about 40 ft. Upgrading from 1/2 in costs $500–$1,500.
Why is my tankless water heater not hot enough?
Almost always an undersized unit for the actual rise, or a flow rate above its capacity: the heater caps its output and the water arrives warm. Check that total GPM is under the rating for your inlet temperature.
How long does a tankless water heater last?
About 20 years with annual descaling in hard water, against 8–12 for a tank. Descaling kits run $50–$150 and take an hour a year.
Method and sources
- Tankless sizing: BTU/h = GPM x temperature rise x 500.