Grease Trap Calculator

Enter the kitchen flow rate and retention time to estimate the grease trap size.

=
Quick answer: with the default inputs (20 GPM, 10 min), the grease trap size is 200. Change any input to update the result.
Grease trap size
—

What the number means

The result is the working volume of an outdoor grease interceptor in gallons. It comes from the peak flow through the kitchen multiplied by the minutes the wastewater has to sit still for the grease to float out. At the defaults, 20 GPM held for 10 minutes is 200 gallons.

The formula

C=Q·tC=Q\,t

Flow rate in gallons per minute times minutes gives gallons. The retention time is the dwell: at 20 GPM a 200 gal trap replaces its whole contents every 10 minutes, and any grease that has not floated by then leaves with the water. The two terms multiply because doubling either one doubles the tank.

Retention is the term that gets argued about. Ten minutes is a common minimum for a small restaurant, 15 for a kitchen with a dish machine, and 20–30 where the menu is heavy on fried food. Moving from 10 to 20 minutes at the same 20 GPM doubles the tank from 200 to 400 gal, so confirm the number with the local health department before ordering a unit.

Flow rate is not the supply pipe size and not the drain size. It is what the fixtures actually discharge when they run together: a 3-compartment sink at about 12 GPM, a pre-rinse spray valve at 1.5 GPM, and a conveyor dish machine at 8 GPM reach roughly 20 GPM if the dish pit is working flat out. Size for that moment, not for the average of the lunch shift.

Worked example at the defaults

20 GPM × 10 min = 200 gal, which happens to be a standard catalogue size, so nothing needs rounding. The same kitchen at 15 minutes of retention would need 300 gal and at 20 minutes 400 gal, both also standard.

  • Default: 20 GPM × 10 min = 200 gal
  • Heavier menu: 20 GPM × 15 min = 300 gal
  • Heavy frying: 20 GPM × 20 min = 400 gal
  • Peak doubled: 40 GPM × 10 min = 400 gal

Note that 20 GPM at 20 minutes and 40 GPM at 10 minutes both land on 400 gal, and they are not the same trap. The first holds water twice as long; the second has twice the surface area and skimming load. A trap sized by doubling the flow needs a larger grease cap and more frequent pumping even though the gallon figure is identical.

Sizing from seats and meals

If you know the dining room rather than the plumbing, convert meals into flow. At 5 gal of wastewater per meal including dishwashing, 240 meals in the dinner hour is 1,200 gal per hour, which is 20 GPM. That is the default flow, and it lands on the 200 gal trap.

The 240 meals can be a 120-seat room turning twice in the hour or a 150-seat room at 1.6 turns. Seats alone do not size a trap; turns and menu do. A 200-seat banquet hall that serves the same 240 meals in 30 minutes pushes 480 meals per hour, which is 2,400 gal per hour, or 40 GPM, and doubles both the flow and the trap.

Converting meals to gallons per minute

The conversion is meals in the peak hour × gallons per meal ÷ 60. At 240 meals and 5 gal, that is 1,200 ÷ 60 = 20 GPM. A menu with a dish machine and no fryer drops to about 3 gal per meal, which gives 12 GPM, and a fried-food menu with heavy floor washing can reach 7 gal per meal, or 28 GPM.

Capacity by flow and retention

Flow10 min15 min20 min
10 GPM100 gal150 gal200 gal
20 GPM200 gal300 gal400 gal
30 GPM300 gal450 gal600 gal
50 GPM500 gal750 gal1,000 gal
75 GPM750 gal1,125 gal1,500 gal

Standard interceptors step through 10, 15, 20, 25, 35, 50, 75, 100, 150, 200, 300, 500, 750, 1,000, 1,500 and 2,000 gal, so a computed 1,125 rounds to 1,500 and a computed 450 rounds to 500. Read the row for your flow and take the next standard size above the cell, never below it.

Code minimums that override the maths

Many plumbing codes set a floor for restaurant traps regardless of the computed volume, commonly 750 or 1,000 gal for a full-service kitchen. A computed 200 gal is legal in some jurisdictions and half the required floor in others, so the arithmetic is the start of the conversation with the inspector, not the end.

Indoor traps and under-sink units

A hydromechanical unit under a 3-compartment sink is a different product with a different rating. Those are rated in pounds of grease capacity, typically 10–50 lb, and in flow, typically 10–25 GPM. This formula sizes the outdoor concrete or steel interceptor, not the small indoor can.

A garbage disposal changes the answer again. Grinding food sends solids to the trap, and some codes respond by requiring 2,500 gal or a larger interceptor plus more frequent pumping. If the kitchen has a disposal, size as though the flow were 1.5 times the fixture total.

What undersizing costs

  • Grease carryover into the sewer, which is the failure that inspectors test for and that cities bill for.
  • Pumping every 3–4 weeks instead of every 2–3 months, at $150–$400 a visit.
  • Odour at the dish pit and backups that close a kitchen faster than a failed inspection.
  • A replacement interceptor, because a tank that is too small cannot be made larger in place.

A 200 gal trap in a busy kitchen fills its grease cap in 4–8 weeks. Twelve pump-outs a year at $150–$400 is $1,800–$4,800, against $600–$1,600 for four visits on a correctly sized unit. The extra tank volume usually pays for itself in two years of pumping alone, before the plumbing bills.

Installation rules that affect the size

The interceptor has to sit outdoors or in a ventilated space, with flow entering one end through a baffle and leaving the other. Two-compartment units hold more grease between pump-outs for the same total volume, so a 200 gal two-compartment trap outperforms a 200 gal single-pass unit on the same duty.

Slope the inlet at 1/4 in per ft and keep the run as short as the code allows, since a long flat run cools the waste and drops grease in the pipe before it ever reaches the trap. The outlet has to discharge to the sanitary sewer through a vented line, and the trap needs a cover the pumper can open without tools.

Frequently asked questions

What size grease trap do I need for a restaurant?

Peak flow times retention. A kitchen discharging 20 GPM that needs 10 minutes is 200 gal; at 15 minutes it is 300 gal, and many codes set a 750 gal floor regardless.

How do I calculate grease trap capacity in gallons?

Multiply flow in GPM by retention in minutes. 30 GPM × 15 min = 450 gal, which rounds up to the 500 gal standard size.

How often should a grease trap be pumped?

When grease and solids fill 25% of the depth, typically every 4–8 weeks for a 200 gal trap in a busy kitchen and every 2–3 months for a correctly sized one.

Is a 1,000 gallon grease trap required?

Some codes set 750 or 1,000 gal as a floor for full-service restaurants, and 2,500 gal where a disposal serves the kitchen. A 200 gal calculation can be below those floors.

How many GPM does a 3 compartment sink discharge?

About 12 GPM with all three compartments draining. Add a dish machine at 8 GPM and a spray valve at 1.5 GPM and you are at the 20 GPM default.

Can I install a grease trap under the sink instead?

Only for small volumes. Under-sink units hold 10–50 lb of grease and are rated in pounds, not sized by flow × retention.

What retention time should I use?

10 minutes minimum, 15 with a dish machine, 20–30 for heavy frying. Doubling retention doubles the tank at the same flow.

How much does it cost to pump a grease trap?

$150–$400 per visit. An undersized trap pumped monthly costs $1,800–$4,800 a year against $600–$1,600 quarterly.

Does a garbage disposal change the trap size?

Yes. Grinding food adds solids, and some codes require 2,500 gal or a larger interceptor. A common workaround is sizing at 1.5 times the fixture flow.

What is the difference between a grease trap and an interceptor?

A trap is the small indoor unit at the sink; an interceptor is the large outdoor tank. This formula sizes the outdoor interceptor.

Method and sources

Calculation basis

Cost ranges reflect 2026 U.S. national averages for materials and labor; regional pricing varies, so use results as a planning baseline and confirm with local quotes.

Last updated: November 17, 2026
Formula & data sources
  • Grease trap capacity = flow rate × retention time.